9-26 Examples
MSTR Transaction #3
The Control Block and Data Block registers for the third MSTR must be loaded with the following
data before the MSTR block is executed. This MSTR writes d1-01 through d5-06.
CONTROL BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40590
Operation Code
0001h
0001h = Write to Multiple Registers
40591
Network Error Code
0000h
The error code returned by Modbus Plus
communications
40592
Number of Registers
0017h
Write to 23 consecutive registers
40593
Data Register Code
0280h
0280h = start of dx-xx parameters
40594
Routing 1
0003h
Modbus Plus node address of the drive = 0003h
40595
Routing 2
0001h
End of routing path = 0001h (Modbus Plus
requirement)
40596
Routing 3
0000h
This routing register is not used, must be set to 0
40597
Routing 4
0000h
This routing register is not used, must be set to 0
40598
Routing 5
0000h
This routing register is not used, must be set to 0
DATA BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40600
d1-01
WRITE
Frequency Reference 1
40601
d1-02
WRITE
Frequency Reference 2
?
?
?
?
40621
d5-05
WRITE
Speed Limit Bias
40622
d5-06
WRITE
Speed/Torque Control Switching Timer