Examples 9-19

MSTR Transaction #1


In this example, the MSTR blocks are executed sequentially. The Control Block registers for the
first MSTR must be loaded with the following data before the MSTR block is executed. This
MSTR reads b1-01 through b9-02.

CONTROL BLOCK

Register

Number

Register

Description

Register

Data

Data

Description

40260

Operation Code

0002h

0002h = Read from Multiple Registers

40261

Network Error Code

0000h

The error code returned by Modbus Plus
communications

40262

Number of Registers

0026h

Read from 38 consecutive registers

40263

Data Register Code

0180h

0180h = start of bx-xx parameters.

40264

Routing 1

0003h

Modbus Plus node address of the drive = 0003h

40265

Routing 2

0001h

End of routing path = 0001h (Modbus Plus
requirement)

40266

Routing 3

0000h

This routing register is not used, must be set to 0

40267

Routing 4

0000h

This routing register is not used, must be set to 0

40268

Routing 5

0000h

This routing register is not used, must be set to 0


The Data Block registers for the first MSTR will be filled with the following data after the MSTR is
completed.

DATA BLOCK

Register

Number

Register

Description

Register

Data

Data

Description

40270

b1-01

READ

Reference Selection

40271

b1-02

READ

Operation Method Selection

?

?

?

?

40306

b9-01

READ

Zero-Servo Gain

40307

b9-02

READ

Zero-Servo Completion Width