MSTR Transaction #1
In this example, the MSTR blocks are executed sequentially. The Control Block registers for the
first MSTR must be loaded with the following data before the MSTR block is executed. This
MSTR reads b1-01 through b9-02.
CONTROL BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40260
Operation Code
0002h
0002h = Read from Multiple Registers
40261
Network Error Code
0000h
The error code returned by Modbus Plus
communications
40262
Number of Registers
0026h
Read from 38 consecutive registers
40263
Data Register Code
0180h
0180h = start of bx-xx parameters.
40264
Routing 1
0003h
Modbus Plus node address of the drive = 0003h
40265
Routing 2
0001h
End of routing path = 0001h (Modbus Plus
requirement)
40266
Routing 3
0000h
This routing register is not used, must be set to 0
40267
Routing 4
0000h
This routing register is not used, must be set to 0
40268
Routing 5
0000h
This routing register is not used, must be set to 0
The Data Block registers for the first MSTR will be filled with the following data after the MSTR is
completed.
DATA BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40270
b1-01
READ
Reference Selection
40271
b1-02
READ
Operation Method Selection
?
?
?
?
40306
b9-01
READ
Zero-Servo Gain
40307
b9-02
READ
Zero-Servo Completion Width