Bit 3 is used to select the function for terminal 4. The function for terminal 4 is determined by the
setting of parameter H1-02.

Bit 4 is used to select the function for terminal 5. The function for terminal 5 is determined by the
setting of parameter H1-03.

Bit 5 is used to select the function for terminal 6. The function for terminal 6 is determined by the
setting of parameter H1-04.

Bit 6 is used to select the function for terminal 7. The function for terminal 7 is determined by the
setting of parameter H1-05.

Bit 7 is used to select the function for terminal 8. The function for terminal 8 is determined by the
setting of parameter H1-06.

Bit 8 is used to cause an external fault. To cause an external fault, this bit should be set to a ‘1’.

Bit 9 is used to reset drive faults that have occurred. To allow the drive to run, this bit should be
set to a ‘0’. To reset a drive fault, this bit should be momentarily set to a ‘1’. To reset a fault, the
run/stop bits (Bit 0 and Bit 1) must also be a ‘0’.