8-4 Diagnostics and Troubleshooting
VS-616G5 Failure Codes
The VS-616G5 drive can have a drive failure, such as undervoltage, overload, external fault, etc.
When a drive failure occurs, it can be classified as an alarm, a minor fault, or a major fault. The
drive reacts differently with each type of failure. An alarm displays a warning indication, however
operation continues. Minor faults allow continued operation, and a contact will close only if one of
the multi-function outputs is set up as a minor fault contact. The major faults cause the motor to
coast to stop, and the fault signal output is present at terminals 18 - 20.
The VS-616G5’s parameters U2-01 (current fault), U2-02 (last fault), and U3-01 (most recent)
display a fault code representing the drive failure. Using the U2-xx and U3-xx registers can aid
greatly in troubleshooting the VS-616G5.
The following table indicates the abbreviation displayed on the Digital Operator and the
hexadecimal code viewed in drive parameters: U2-01, U2-02, and U3-01 when a specific drive
failure occurs. The table also indicates whether the drive failure is an A-alarm, m-minor fault, or
M-major fault.
Drive Failure
Digital Operator
Display
Hexadecimal
Code
Alarm, minor fault, or
Major Fault
DC Bus Fuse Open
PUF
1
M
DC Bus Undervoltage
UV1
2
A
CTL PS Undervoltage
UV2
3
A
MC Answerback
UV3
4
A
Short Circuit
SC
5
M
Ground Fault
GF
6
M
Overcurrent
oC
7
M
Overvoltage
oV
8
M
Heatsink Overtemperature
oH
9
M
Drive Overheat
oH1
A
M
Motor Overload
oL1
B
M
Drive Overload
oL2
C
M
Overtorque 1
oL3
D
M
Overtorque 2
oL4
E
M
Dynamic Braking Transistor
RR
F
M
Dynamic Braking Resistor
RH
10
M
External Fault 3
EF3
11
M
External Fault 4
EF4
12
m
External Fault 5
EF5
13
m
External Fault 6
EF6
14
m
External Fault 7
EF7
15
m
External Fault 8
EF8
16
m
reserved
17
-
Overspeed
oS
18
M
Speed Deviation
DEV
19
m
PG Open
PGo
1A
M
Input Phase Loss
PF
1B
M
Output Phase Loss
LF
1C
M
DCCT Fault
CF
1D
M
Operator Disconnected
-
1E
m
EEPROM R/W Error
ERR
1F
m
reserved
20
-
Modbus Com Error
CE
21
M
reserved
22 - 24
-
Control Fault
CPFxx
25
M
Zero Servo Fault
SVE
26
-
DDS External Fault
EF0
27
-
Note: Further detail on drive failures and troubleshooting can be found in Chapter 4 of the VS-616G5
Installation & Quick-Start Manual, YEA-TOA-S616-10.12.