8-4 Diagnostics and Troubleshooting

VS-616G5 Failure Codes

The VS-616G5 drive can have a drive failure, such as undervoltage, overload, external fault, etc.
When a drive failure occurs, it can be classified as an alarm, a minor fault, or a major fault. The
drive reacts differently with each type of failure. An alarm displays a warning indication, however
operation continues. Minor faults allow continued operation, and a contact will close only if one of
the multi-function outputs is set up as a minor fault contact. The major faults cause the motor to
coast to stop, and the fault signal output is present at terminals 18 - 20.

The VS-616G5’s parameters U2-01 (current fault), U2-02 (last fault), and U3-01 (most recent)
display a fault code representing the drive failure. Using the U2-xx and U3-xx registers can aid
greatly in troubleshooting the VS-616G5.

The following table indicates the abbreviation displayed on the Digital Operator and the
hexadecimal code viewed in drive parameters: U2-01, U2-02, and U3-01 when a specific drive
failure occurs. The table also indicates whether the drive failure is an A-alarm, m-minor fault, or
M-major fault.

Drive Failure

Digital Operator

Display

Hexadecimal

Code

Alarm, minor fault, or

Major Fault

DC Bus Fuse Open

PUF

1

M

DC Bus Undervoltage

UV1

2

A

CTL PS Undervoltage

UV2

3

A

MC Answerback

UV3

4

A

Short Circuit

SC

5

M

Ground Fault

GF

6

M

Overcurrent

oC

7

M

Overvoltage

oV

8

M

Heatsink Overtemperature

oH

9

M

Drive Overheat

oH1

A

M

Motor Overload

oL1

B

M

Drive Overload

oL2

C

M

Overtorque 1

oL3

D

M

Overtorque 2

oL4

E

M

Dynamic Braking Transistor

RR

F

M

Dynamic Braking Resistor

RH

10

M

External Fault 3

EF3

11

M

External Fault 4

EF4

12

m

External Fault 5

EF5

13

m

External Fault 6

EF6

14

m

External Fault 7

EF7

15

m

External Fault 8

EF8

16

m

reserved

17

-

Overspeed

oS

18

M

Speed Deviation

DEV

19

m

PG Open

PGo

1A

M

Input Phase Loss

PF

1B

M

Output Phase Loss

LF

1C

M

DCCT Fault

CF

1D

M

Operator Disconnected

-

1E

m

EEPROM R/W Error

ERR

1F

m

reserved

20

-

Modbus Com Error

CE

21

M

reserved

22 - 24

-

Control Fault

CPFxx

25

M

Zero Servo Fault

SVE

26

-

DDS External Fault

EF0

27

-

Note: Further detail on drive failures and troubleshooting can be found in Chapter 4 of the VS-616G5
Installation & Quick-Start Manual, YEA-TOA-S616-10.12.