Yaskawa VS-616G5 Modbus Plus Communication Card User Manual

Page 82

background image

Data Registers



A-2

Global Write Registers (write only)


REGISTER

FUNCTION

BIT

DATA

DESCRIPTION

(in hex)

NO.

SET

001h *

Operational Command

0

0

Stop Forward

1

Run Forward

1

0

Stop Reverse

1

Run Reverse

2

Terminal 3 Function

3

Terminal 4 Function

4

Terminal 5 Function

5

Terminal 6 Function

6

Terminal 7 Function

7

Terminal 8 Function

8

1

External Fault

9

1

Fault Reset

002h *

Frequency Reference

Frequency Reference (6000 = 60.00Hz) (1)


(1) Scaling depends on the setting of o1-03
* If parameter o2-09 is not set to ‘1’; then the operation signals register and frequency reference register will not be ‘1’ and ‘2’ respectively.