Mstr transaction #1 – Yaskawa VS-616G5 Modbus Plus Communication Card User Manual
Page 74

9-30 Examples
MSTR Transaction #1
In this example, the MSTR blocks are executed simultaneously. The Control Block registers for
the first MSTR must be loaded with the following data before the MSTR block is executed. This
MSTR reads drive status from drive #2.
CONTROL BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40680
Operation Code
0002h
0002h = Read from Multiple Registers
40681
Network Error Code
0000h
The error code returned by Modbus Plus
communications
40682
Number of Registers
0010h
Read from 16 consecutive registers
40683
Data Register Code
F000h
F000h = Drive Status Signals
40684
Routing 1
0002h
Modbus Plus node address of the drive = 0002h
40685
Routing 2
0001h
End of routing path = 0001h (Modbus Plus
requirement)
40686
Routing 3
0000h
This routing register is not used, must be set to 0
40687
Routing 4
0000h
This routing register is not used, must be set to 0
40688
Routing 5
0000h
This routing register is not used, must be set to 0
The Data Block registers for the first MSTR will be filled with the following data after the MSTR is
completed.
DATA BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40690
Drive Status Signals
READ
RUN/STOP, FWD/REV, Drive Ready, etc.
40691
Motor Speed
READ
Motor Speed
40692
Torque Reference
READ
Torque Reference
40693
not used
n/a
n/a
40694
Speed Reference
READ
Frequency command to drive
40695
Output Frequency
READ
(0.1 Hz) Frequency at the drive
40696
Output Current
READ
Current at the output
40697
Analog Input
READ
Control Circuit Term 14 Input Volatge
40698
DC Bus Voltage
READ
(1.0 V) DC Bus voltage
40699
Fault Content 1
READ
Overcurrent, Overvoltage,
40700
Fault Content 2
READ
Drive Overload,
40701
Fault Content 3
READ
etc.
40702
Analog Input
READ
Control Circuit Term 16 Input Voltage
40703
Digital Input
READ
Input Terminal Status
40704
Analog Input
READ
Control Circuit Term 13 Input Voltage
40705
not used
n/a
n/a