Examples 9-25

MSTR Transaction #2


The Control Block and Data Block registers for the second MSTR must be loaded with the
following data before the MSTR block is executed. This MSTR writes C1-01 through C8-30.

CONTROL BLOCK

Register

Number

Register

Description

Register

Data

Data

Description

40510

Operation Code

0001h

0001h = Write to Multiple Registers

40511

Network Error Code

0000h

The error code returned by Modbus Plus
communications

40512

Number of Registers

0040h

Write to 64 consecutive registers

40513

Data Register Code

0200h

0200h = start of Cx-xx parameters

40514

Routing 1

0003h

Modbus Plus node address of the drive = 0003h

40515

Routing 2

0001h

End of routing path = 0001h (Modbus Plus
requirement)

40516

Routing 3

0000h

This routing register is not used, must be set to 0

40517

Routing 4

0000h

This routing register is not used, must be set to 0

40518

Routing 5

0000h

This routing register is not used, must be set to 0


DATA BLOCK

Register

Number

Register

Description

Register

Data

Data

Description

40520

C1-01

WRITE

Acceleration Time 1

40521

C1-02

WRITE

Deceleration Time 1

?

?

?

?

40583

C8-30

WRITE

Carrier in Tune