Mstr transaction #2 – Yaskawa VS-616G5 Modbus Plus Communication Card User Manual
Page 69

Examples 9-25
MSTR Transaction #2
The Control Block and Data Block registers for the second MSTR must be loaded with the
following data before the MSTR block is executed. This MSTR writes C1-01 through C8-30.
CONTROL BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40510
Operation Code
0001h
0001h = Write to Multiple Registers
40511
Network Error Code
0000h
The error code returned by Modbus Plus
communications
40512
Number of Registers
0040h
Write to 64 consecutive registers
40513
Data Register Code
0200h
0200h = start of Cx-xx parameters
40514
Routing 1
0003h
Modbus Plus node address of the drive = 0003h
40515
Routing 2
0001h
End of routing path = 0001h (Modbus Plus
requirement)
40516
Routing 3
0000h
This routing register is not used, must be set to 0
40517
Routing 4
0000h
This routing register is not used, must be set to 0
40518
Routing 5
0000h
This routing register is not used, must be set to 0
DATA BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40520
C1-01
WRITE
Acceleration Time 1
40521
C1-02
WRITE
Deceleration Time 1
?
?
?
?
40583
C8-30
WRITE
Carrier in Tune