Mstr transaction #2 – Yaskawa VS-616G5 Modbus Plus Communication Card User Manual
Page 61

Examples 9-17
MSTR Transaction #2
The Control Block and Data Block registers for the second MSTR must be loaded with the
following data before the MSTR block is executed. This MSTR writes to the Global Frequency
Reference Multiplier Register on drive #2.
CONTROL BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40240
Operation Code
0001h
0001h = Write to Multiple Registers
40241
Network Error Code
0000h
The error code returned by Modbus Plus
communications
40242
Number of
Registers
0001h
Write to 1 consecutive register
40243
Data Register Code
F201h
Global Write Data Register
40244
Routing 1
0002h
Modbus Plus node address of the drive = 0002h
40245
Routing 2
0001h
End of routing path = 0001h (Modbus Plus
requirement)
40246
Routing 3
0000h
This routing register is not used, must be set to 0
40247
Routing 4
0000h
This routing register is not used, must be set to 0
40248
Routing 5
0000h
This routing register is not used, must be set to 0
DATA BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40250
Global Frequency
Reference Multiplier
01F4h
0500 (decimal) = .500 multiplier. Frequency in
002h register is multiplied by .500 on drive 2.