Data Registers



A-6

Command Registers (Read / Write)

REGISTER

FUNCTION

BIT

DATA

DESCRIPTION

(in hex)

NO.

SET

001h *

Operational Command

0

0

Stop Forward

1

Run Forward

1

0

Stop Reverse

1

Run Reverse

2

Terminal 3 Function (1)

3

Terminal 4 Function (1)

4

Terminal 5 Function (1)

5

Terminal 6 Function (1)

6

Terminal 7 Function (1)

7

Terminal 8 Function (1)

8

1

External Fault

9

1

Fault Reset

002h *

Frequency Reference / Output Frequency

.01 Hz (7)

003h

Torque Reference

Flux Vector mode only (0.1%)

004h

Torque Compensation

Flux Vector mode only (0.1%)

005h

Not Supported

006h

Analog Output 1 Setting

-10V / -660

?

+10V / +660 analog output on terminals 21 & 22 (5)

007h

Analog Output 2 Setting

-10V / -660

?

+10V / +660 analog output on terminals 22 & 23 (6)

008h

Digital Output Setting

0

Multi-function Contact Output (terminals 9 & 10): “closed” (2)

1

Multi-function Contact Output (terminals 25 & 27): “closed” (3)

2

Multi-function Contact Output (terminals 26 & 27): “closed” (4)

3

not used

4

not used

5

not used

6

Fault Contact enable

7

Fault Contact state (effective only when bit 6 = ‘1’)

(1)

The availability of the multi-function input terminals vary depending upon the settings of H1-01, H1-02, H1-03, H1-04, H1-05, H1-06 (the multi-function input settings)

(2) Effective when H2-01 = 0Fh.

(3) Effective when H2-02 = 0Fh.

(4) Effective when H2-03 = 0Fh.

(5) Effective when H4-01 = 1Fh.

(6) Effective when H4-04 = 1Fh.

(7) Desired frequency of 35.75 Hz requires a value of 3575 in register data code 002h. Scaling depends on the setting of o1-03
* If parameter o2-09 is not set to ‘1’; then the operation signals register and frequency reference register will not be ‘1’ and ‘2’ respectively.