Data Registers
A-6
Command Registers (Read / Write)
REGISTER
FUNCTION
BIT
DATA
DESCRIPTION
(in hex)
NO.
SET
001h *
Operational Command
0
0
Stop Forward
1
Run Forward
1
0
Stop Reverse
1
Run Reverse
2
Terminal 3 Function (1)
3
Terminal 4 Function (1)
4
Terminal 5 Function (1)
5
Terminal 6 Function (1)
6
Terminal 7 Function (1)
7
Terminal 8 Function (1)
8
1
External Fault
9
1
Fault Reset
002h *
Frequency Reference / Output Frequency
.01 Hz (7)
003h
Torque Reference
Flux Vector mode only (0.1%)
004h
Torque Compensation
Flux Vector mode only (0.1%)
005h
Not Supported
006h
Analog Output 1 Setting
-10V / -660
?
+10V / +660 analog output on terminals 21 & 22 (5)
007h
Analog Output 2 Setting
-10V / -660
?
+10V / +660 analog output on terminals 22 & 23 (6)
008h
Digital Output Setting
0
Multi-function Contact Output (terminals 9 & 10): “closed” (2)
1
Multi-function Contact Output (terminals 25 & 27): “closed” (3)
2
Multi-function Contact Output (terminals 26 & 27): “closed” (4)
3
not used
4
not used
5
not used
6
Fault Contact enable
7
Fault Contact state (effective only when bit 6 = ‘1’)
(1)
The availability of the multi-function input terminals vary depending upon the settings of H1-01, H1-02, H1-03, H1-04, H1-05, H1-06 (the multi-function input settings)
(2) Effective when H2-01 = 0Fh.
(3) Effective when H2-02 = 0Fh.
(4) Effective when H2-03 = 0Fh.
(5) Effective when H4-01 = 1Fh.
(6) Effective when H4-04 = 1Fh.
(7) Desired frequency of 35.75 Hz requires a value of 3575 in register data code 002h. Scaling depends on the setting of o1-03
* If parameter o2-09 is not set to ‘1’; then the operation signals register and frequency reference register will not be ‘1’ and ‘2’ respectively.