Data Registers

A-11

Monitor Registers (Read only) – continued

REGISTER

FUNCTION

BIT

DESCRIPTION

(in hex)

NO.

F100h

Inverter Status

0

Run

1

Zero-Speed

2

Reverse Run

3

Reset Signal Input

4

Speed Agree

5

Drive Operation Ready

6

Minor Fault

7

Major Fault

8-15

will return zeros

F101h

Operator Status

0

oPE Error

1

not used

2

Program Mode

3

1CN Status:

4

01=JVOP132 / 00=JVOP130(std. operator) / 11=Personal Computer / 10=JVOP100

5-15

not used

F102h

oPE No.

oPE Error Code (oPE01=1, oPE02=2, oPE03=3, oPE06=6, oPE10=10, oPE11=11)

F103h

not used

-

F104h

Fault Content 1

0

Fuse Blown (FU)

1

DC Bus Undervoltage (UV1)

2

Control Power Supply Undervoltage (UV2)

3

Main Circuit Answerback (UV3)

4

Short Circuit (SC)

5

Ground Fault (GF)

6

Overcurrent (oC)

7

Overvoltage (oV)

8

Heatsink Overtemperature (oH)

9

Drive Overheat (oH1)

10

Motor Overload (oL1)

11

Drive Overload (oL2)

12

Overtorque 1 (oL3)

13

Overtorque 2 (oL4)

14

Dynamic Braking Transistor (RR)

15

Dynamic Braking Resistor (RH)