Mounting, Hardware, Dimensions – Basler Electric DGC-2020ES User Manual
Page 95: Cutout
9469200990 Rev C
87
Mounting
DGC-2020ES controllers are delivered in sturdy cartons to prevent shipping damage. Upon receipt of a
unit, check the part number against the requisition and packing list for agreement. Inspect for damage,
and if there is evidence of such, immediately file a claim with the carrier and notify the Basler Electric
regional sales office or your sales representative.
If the device is not installed immediately, store it in the original shipping package in a moisture- and dust-
free environment.
Hardware
The front panel is resistant to moisture, salt fog, humidity, dust, dirt, and chemical contaminants. DGC-
2020ES controllers are mounted using the four permanently attached 10-24 studs. The torque applied to
the mounting hardware should not exceed 20 inch-pounds (2.2 newton meters).
Dimensions
Panel cutting and drilling dimensions are shown in Figure 46. Overall dimensions are shown in Figure 47.
All dimensions are shown in inches with millimeters in parenthesis.
Figure 46. Panel Cutting and Drilling Dimensions
P0067-98
7.433 (188.8) max
7.393 (187.8) min
7.635 (194.0) max
7.615 (193.4) min
5.635 (143.2) max
5.615 (142.6) min
5.433 (138) max
5.393 (137) min
0.218 (5.5) diameter
CUTOUT
0.242 (6.2) max
0.182 (4.6) min
0.242 (6.2) max
0.182 (4.6) min
0.320 (8.1) max
0.280 (7.1) min
45°
DGC-2020ES
Mounting