beautypg.com

Basler Electric DGC-2020ES User Manual

Page 136

background image

128

9469200990 Rev C

Name

Description

Symbol

Latches

Reset Priority
Latch

When the Set input is on and the Reset input is off, the latch will go to
the SET (ON) state. When the Reset input is on and the Set input is
off, the latch will go to the RESET (OFF) state. If both the Set and
Reset inputs are on at the same time, a reset priority latch will go to the
RESET (OFF) state.

Set Priority
Latch






When the Set input is on and the Reset input is off, the latch will go to
the SET (ON) state. When the Reset input is on and the Set input is
off, the latch will go to the RESET (OFF) state. If both the Set and
Reset inputs are on at the same time, a set priority latch will go to the
SET (ON) state.

Other

Comment
Block

Enter user comments.

Elements

This group contains elements for the 27, 47, 50, 59, and 81. It also contains elements for Generator
Breaker, Mains Breaker, Logic Alarm, Logic Pre-Alarm, Configurable Elements, AUTO Mode, OFF Mode,
RUN Mode, Run with Load, Engine Run, ATS, Run Inhibit, Test Inhibit, Pre-Start Output, Start Output,
Run Output, Cool Stop Request, Cool Down Request, External Start Delay, Start Delay Bypass, Alternate
Frequency Override, Mains Fail Test, Load Take Over, EPS Supplying Load, MTU Speed Demand
Switch, Reset, Alarm Silence, Lamp Test, Idle Request, Low Fuel Pre-Alarm, Diesel Particulate Filter
Manual Regeneration, Diesel Particulate Filter Regeneration Inhibit, Emergency Stop, Speed Raise,
Speed Lower, MTU Cylinder Cutout Disable, and Automatic Breaker Operation Inhibit from PLC.

Table 25 lists the names and descriptions of the elements in the Elements group.

Table 25. Elements Group, Names and Descriptions

Name

Description

Symbol

Protection

27TRIP

True when the 27-1 undervoltage is in a TRIP condition.
Connect to another logic block input.

47TRIP

True when the 47 phase imbalance is in a TRIP condition.
Connect to another logic block input.

50TRIP

True when the 50 overcurrent is in a TRIP condition.
Connect to another logic block input.

59TRIP

True when the 59-1 overvoltage is in a TRIP condition.
Connect to another logic block input.

BESTlogic

Plus

DGC-2020ES