Setting the time and date, Real-time clock specifications – Basler Electric DGC-2020ES User Manual
Page 176
![background image](https://www.manualsdir.com/files/773946/content/doc176.png)
168
9469200990 Rev C
Table 31. Settings for Clock
Setting
Range
Increment
Unit
Default
UTC Offset
–1,440 to 1,440
1
minutes
–6
DST Configuration
Floating Dates or Fixed Dates
n/a
n/a
Disabled
Start/End Time
Reference
Respective to Local Time or
Respective to UTC Time
n/a
n/a
Respective to
Local Time
Bias Setup (Hour)
–12 to 12
1
hours
Disabled
Bias Setup (Minute)
–59 to 59
1
minutes
0
Clock Not Set
Warning
Disable or Enable
n/a
n/a
Disable
Setting the Time and Date
Time and date settings are made through BESTCOMSPlus on the Real Time Clock screen (Figure 87) of
the Metering Explorer. Settings can also be made through the front panel.
Figure 87. Metering Explorer, Real Time Clock Screen
Real-Time Clock Specifications
Resolution ................................................................. 1 s
Accuracy....................................................................
±1.73 s/d at 25°C
Clock Holdup
Capacitor Holdup Time ............................................. Up to 24 hours depending on conditions
Battery Holdup Time ................................................. Approximately ten years depending on conditions
Timekeeping
DGC-2020ES