Basler Electric DGC-2020ES User Manual
Page 130
122
9469200990 Rev C
Name
Description
Symbol
Global Alarm
True when one or more alarms are set.
Global Sender
Fail
True when one or more of the Sender Fails are
configured as alarms and are true.
Hi Coolant
Temp
True when the High Coolant Temp Alarm settings have
been exceeded.
Low Coolant
Level
True when the Low Coolant Level function is
configured as an alarm and the activation delay has
expired. In addition, true when CAN Bus is enabled
and the Low Coolant Level Alarm threshold has been
exceeded.
Low Fuel Level
True when the Low Fuel Level Alarm settings have
been exceeded.
Low Oil
Pressure
True when the Low Oil Pressure Alarm settings have
been exceeded.
Oil Pressure
Sender Fail
True when the Oil Pressure Sender Fail is configured
as an alarm and the activation delay has expired.
Overcrank
True when an Overcrank condition exists.
Overspeed
True when the Overspeed Alarm settings have been
exceeded.
Speed Sender
Fail
True when the Speed Sender Fail activation delay has
expired.
Unexpected
Shutdown
Alarm
True when the metered engine speed (RPM)
unexpectedly drops to 0 while the engine is running.
Voltage Sensing
Fail
True when the Voltage Sensing Fail is configured as
an alarm and the activation delay has expired.
Pre-Alarms
Battery Charger
Fail
True when the Battery Charger Fail function is
configured as a pre-alarm and the activation delay has
expired.
Battery
Overvoltage
True when the Battery Overvoltage pre-alarm threshold
has been exceeded.
Checksum
Failure
True when some of the user settings or firmware code
has been corrupted. Refer to the Reporting and Alarms
chapter for more details.
Contact
Expansion
Module
Multiple Contact
Expansion
Modules
Connected
True when more than one CEM-2020 is connected.
BESTlogic
™Plus
DGC-2020ES