beautypg.com

Basler Electric DGC-2020ES User Manual

Page 130

background image

122

9469200990 Rev C

Name

Description

Symbol

Global Alarm

True when one or more alarms are set.

Global Sender
Fail

True when one or more of the Sender Fails are
configured as alarms and are true.

Hi Coolant
Temp

True when the High Coolant Temp Alarm settings have
been exceeded.

Low Coolant
Level

True when the Low Coolant Level function is
configured as an alarm and the activation delay has
expired. In addition, true when CAN Bus is enabled
and the Low Coolant Level Alarm threshold has been
exceeded.

Low Fuel Level

True when the Low Fuel Level Alarm settings have
been exceeded.

Low Oil
Pressure

True when the Low Oil Pressure Alarm settings have
been exceeded.

Oil Pressure
Sender Fail

True when the Oil Pressure Sender Fail is configured
as an alarm and the activation delay has expired.

Overcrank

True when an Overcrank condition exists.

Overspeed

True when the Overspeed Alarm settings have been
exceeded.

Speed Sender
Fail

True when the Speed Sender Fail activation delay has
expired.

Unexpected
Shutdown
Alarm

True when the metered engine speed (RPM)
unexpectedly drops to 0 while the engine is running.

Voltage Sensing
Fail

True when the Voltage Sensing Fail is configured as
an alarm and the activation delay has expired.

Pre-Alarms

Battery Charger
Fail

True when the Battery Charger Fail function is
configured as a pre-alarm and the activation delay has
expired.

Battery
Overvoltage

True when the Battery Overvoltage pre-alarm threshold
has been exceeded.

Checksum
Failure

True when some of the user settings or firmware code
has been corrupted. Refer to the Reporting and Alarms
chapter for more details.

Contact
Expansion
Module
Multiple Contact
Expansion
Modules
Connected

True when more than one CEM-2020 is connected.

BESTlogic

Plus