Basler Electric DGC-2020ES User Manual
Page 29

9469200990 Rev C
21
■
OPEN CMD (Visible when configured.)
■
CLOSE CMD (Visible when configured.)
○
BRK CLOSE FAIL PALM
○
BRK OPEN FAIL PALM
●
BUS CONDITION DETECT
○
GEN DEAD
■
THRESHOLD
■
TIME DELAY
○
GEN STABLE
■
OV PICKUP
■
OV DROPOUT
■
UV PICKUP
■
UV DROPOUT
■
OF PICKUP
■
OF DROPOUT
■
UF PICKUP
■
UF DROPOUT
■
TIME DELAY
■
LOW LINE SF (Visible when an input is selected for the Low Line Override programmable
function.)
■
ALT FREQ SF
○
GEN FAILED
■
TIME DELAY
○
BUS DEAD
■
THRESHOLD
■
TIME DELAY
○
BUS STABLE
■
OV PICKUP
■
OV DROPOUT
■
UV PICKUP
■
UV DROPOUT
■
OF PICKUP
■
OF DROPOUT
■
UF PICKUP
■
UF DROPOUT
■
TIME DELAY
■
LOW LINE SF (Visible when an input is selected for the Low Line Override programmable
function.)
■
ALT FREQ SF
○
BUS FAILED
■
TIME DELAY
LOGIC TIMERS
●
TIMER X (X = 1 to 10)
○
HOURS
○
MINUTES
○
SECONDS
ENTER PASSWORD
LOGOUT (Visible when logged in through the front panel.)
One-Line Diagram
A one-line diagram of the breaker hardware configuration can be displayed on the front panel. This
diagram changes in real time to reflect the current state of the configured breakers. The one-line diagram
is disabled by default. To display the one-line diagram using front panel controls, navigate to Settings >
General Settings > Front Panel HMI > One-Line Diagram and enable the setting. If using
BESTCOMSPlus, navigate to Settings Explorer, General Settings, Front Panel HMI and select Enable on
the One-Line Diagram setting.
DGC-2020ES
Controls and Indicators