222

9469200990 Rev C

DEF INDUCEMENT OVERRIDE: This pre-alarm displays when SPN 5246 has a value of 6, indicating
the Temporary Override of inducement. This indicates DEF inducement is temporarily overridden.
The engine may operate with reduced power, or for a limited time, after which time it may re-enter the
SEVERE INDUCEMENT state.

Exit Conditions for DEF Severe Inducement

First Restart: Return to 0% torque reduction in exit condition, until proper DEF level and quality
evaluation. If low level or poor DEF quality is detected during the next monitoring cycle, the severe
inducement will be active after the next restart. After the second restart, a service tool is required to
exit the severe inducement.

With Service Tool Clearing: Invoke 0% torque reduction with service tool clearing until proper DEF
level and quality evaluation. If low level or poor DEF quality is detected during the next monitoring
cycle, the severe inducement will be active after the next restart.

Exhaust Treatment

DGC-2020ES