Basler Electric DGC-2020ES User Manual
Page 127

9469200990 Rev C
119
Name
Description
Symbol
Status Input
Generator
Protection
True when the 81 Under element is tripped.
Status Input
Generator
Reverse
Rotation
True when the generator rotation is opposite of the
Phase Rotation setting.
Status Input
Generator
Stable
True when the Gen Stable condition settings have
been exceeded.
Status Input
Generator Test
Loaded
True when the Exercise Timer has started the
generator and run with load is selected.
Status Input
Generator Test
True when the Exercise Timer has started the
generator.
Status Input
Global Low
Coolant Level
True when the Low Coolant Level input is true.
Status Input
Ground Delta
Override
True when the Grounded Delta Override input is true.
Status Input
Idle Request
True when the Idle Request logic element is true.
Status Input
In Alarm State
True when the DGC-2020ES is in the alarm state.
Status Input
In Connecting
State
True when the DGC-2020ES is in the connecting state.
Status Input
In Cooling State
True when the DGC-2020ES is in the cooling state.
Status Input
In Cranking
State
True when the DGC-2020ES is in the cranking state.
Status Input
In Disconnect
State
True when the DGC-2020ES is in the disconnect state.
Status Input
In Prestart State
True when the DGC-2020ES is in the pre-start state.
Status Input
In Pulsing State
True when the DGC-2020ES is in the pulsing state.
Status Input
In Ready State
True when the DGC-2020ES is in the ready state.
Status Input
In Resting State
True when the DGC-2020ES is in the resting state.
Status Input
In Running
State
True when the DGC-2020ES is in the running state.
DGC-2020ES
BESTlogic
™Plus