Name
Description
Symbol
81TRIP
True when the 81 frequency is in a TRIP condition. Connect
to another logic block input.
Other
ALARMSILENCE
The alarm will be silenced when this element is true. The
alarm can also be silenced by pressing the Alarm Silence
button on the front panel of the DGC-2020ES.
ALTFREQOVER
When this logic element is true, protection and bus condition
detection is forced to operate at the Alternate Frequency
instead of the Rated Frequency.
ATS
When this logic element is true, and the DGC-2020ES is in
AUTO mode, the generator will run. This can be used in
place of the ATS programmable function if it is desired to
generate the ATS signal as a combination of programmable
logic rather than a simple contact input. If either the ATS
logic element is true or the contact mapped to the ATS
programmable function is true, and the DGC-2020ES is in
AUTO mode, the generator will run. If both the ATS logic
element and the ATS programmable function are false, and
the DGC-2020ES is in AUTO mode, the generator will cool
down and stop.
AUTOMODE
When this input is true, and the DGC-2020ES is in OFF
mode, the DGC-2020ES will switch to AUTO mode. This is
a pulsed input. It does not need to be held after the desired
mode switch has occurred.
AUTOBRKOP-
INHIBIT
Automatic breaker operation is inhibited when the Set input
is true.
CONFELMNTX
(X = 1 to 8)
Configurable elements (CONFELMNT1-8) are connected to
the logic scheme as outputs. These elements are
configurable in BESTCOMSPlus under Programmable
Outputs, Configurable Elements. The user can assign a
string of up to 16 characters, configure whether the element
should generate an alarm or pre-alarm. If used for alarm or
pre-alarm, the user's text is what will appear in the alarm or
pre-alarm annunciation and in the DGC-2020ES event log.