Basler Electric DGC-2020ES User Manual
Page 163

9469200990 Rev C
155
Rated Volts (V L-L)
This setting accepts values from 1 to 99,999, in increments of 1.
Rated Power Factor (PF)
This setting accepts values from -1 to 1, in increments of 0.001.
Genset kW Rating
This setting accepts values from 5 to 9,999, in increments of 1.
Rated Engine RPM
This setting accepts values from 750 to 3,600, in increments of 1.
Calculated Rated Data
Rated Secondary Volts, Rated Phase Amps, Rated Secondary Phase Amps, Rated kVA, and Rated kvar
are calculated automatically. The equations used for these calculations are listed below.
=
Volts
Primary
PT
Gen
Volts
Secondary
PT
Gen
Volts
Rated
Volts
Secondary
Rated
Error! Bookmark not defined.
3
Volts
L
L
Rated
kVA
Rated
machine)
phase
(3
Amps
Phase
Rated
−
=
−
Volts
L
L
Rated
kVA
Rated
machine)
phase
(1
Amps
Phase
Rated
−
=
−
=
Amps
Primary
CT
Amps
Secondary
CT
Amps
Phase
Rated
Amps
Phase
Secondary
Rated
PF
Rated
kW
Rated
kVA
Rated
=
2
PF
Rated
1
kVA
Rated
kvar
Rated
−
=
Frequency
The frequency settings allow selection of the rated frequency of the generator and an alternate frequency.
Rated Frequency of the Unit
Rated frequency settings consist of 50 and 60 Hz.
Alternate Frequency
This setting accepts values from 10 to 450, in increments of 0.01.
Battery Volts
The nominal voltage of the starter battery is used by the DGC-2020ES to detect and annunciate battery
overvoltage and low or weak battery voltage. The Battery Volts settings consist of 12 V and 24 V.
Generator Connection
Genset connection types accommodated by the DGC-2020ES include three, three-phase connections
(delta, wye, and grounded delta) and a single-phase configuration (sensing across phases A and B.)
DGC-2020ES
Configuration