Remote contact input configuration, Remote contact output configuration – Basler Electric DGC-2020ES User Manual
Page 202
194
9469200990 Rev C
Remote Contact Input Configuration
The CEM-2020 provides 10 contact inputs. Each of the 10 contact inputs can be independently
configured to annunciate an alarm or pre-alarm when the input senses a contact closure. A user-
adjustable time delay can be set to delay recognition of a contact input. By default, all inputs are
configured so that they do not trigger an alarm or pre-alarm.
To make identifying the contact inputs easier, a user-assigned name can be given to each input.
Contacts can be recognized always or only while the engine is running.
The remote contact inputs are incorporated into a BESTlogicPlus programmable logic scheme by
selecting them from the I/O group in BESTlogicPlus. For more details, refer to the BESTlogicPlus chapter.
Remote contact input status is available in BESTlogicPlus Programmable Logic when “None” is selected
for Alarm Configuration.
The Remote Contact Inputs screen is found in the BESTCOMSPlus Settings Explorer under the
Programmable Inputs category. If using the front panel, navigate to Settings > Programmable Inputs >
Configurable Inputs. The BESTCOMSPlus Remote Contact Inputs screen is illustrated in Figure 94.
Figure 94. Settings Explorer, Programmable Inputs, Remote Contact Inputs Screen
Remote Contact Output Configuration
To make identifying the contact outputs easier, each of the contact outputs can be given a user-assigned
name.
The contact outputs are incorporated into a BESTlogicPlus programmable logic scheme by selecting
them from the I/O group in BESTlogicPlus. For more details, refer to the BESTlogicPlus chapter.
The Remote Contact Outputs screen is found in the BESTCOMSPlus Settings Explorer under the
Programmable Inputs category. If using the front panel, navigate to Settings > Programmable Outputs >
Configurable Outputs. The BESTCOMSPlus Contact Outputs screen is illustrated in Figure 95.
CEM-2020
DGC-2020ES