Basler Electric DGC-2020ES User Manual
Page 198

190
9469200990 Rev C
Operating Power
The Contact Expansion Module operating power input accepts either 12 Vdc or 24 Vdc and tolerates
voltage over the range of 6 to 32 Vdc. Operating power must be of the correct polarity. Although reverse
polarity will not cause damage, the CEM-2020 will not operate. Operating power terminals are listed in
Table 32.
It is recommended that a fuse be added for additional protection for the wiring to the battery input of the
Contact Expansion Module. A Bussmann ABC-7 fuse or equivalent is recommended.
Table 32. Operating Power Terminals
Terminal
Description
P1-
(SHIELD)
Chassis ground connection
P1- – (BATT–)
Negative side of operating power input
P1 + (BATT+)
Positive side of operating power input
Contact Inputs and Contact Outputs
The CEM-2020 (Figure 90) has 10 contact inputs and 24 contact outputs. The CEM-2020H (Figure 91)
has 10 contact inputs and 18 contact outputs.
Note
To follow UL guidelines, a fuse must be implemented in the 2Adc
contact circuits (Outputs 5 through 16) of the CEM-2020H used in
hazardous locations. The suggested fuse size in Adc = (100/Contact
Voltage) with a maximum fuse size of 5Adc.
CEM-2020
DGC-2020ES