84
9469200990 Rev C
Event String
Event Description
Event Type
HIGH OIL TERMPERATURE A
High Oil Temp
Alarm
HIGH STRG TANK LEVEL P
High Storage Tank Level
Pre-Alarm
IDLE SPD LO P
Idle Speed Low
Pre-Alarm
INPUT X A (X = 1 to 17)
User Configurable Input X (X = 1 to 17)
Alarm
INPUT X P (X = 1 to 17)
User Configurable Input X (X = 1 to 17)
Pre-Alarm
LO AFTERCLR COOL LVL A
Low After Cooler Cool Level
Alarm
LO CHG AIR CLNT LVL P
Low Charge Air Coolant Level
Pre-Alarm
LO DAY TANK LEVEL P
Low Day Tank Level
Pre-Alarm
LO ECU VOLTS P
Low ECU Supply Voltage
Pre-Alarm
LO FUEL DLV PRESSURE A
Low Fuel Delivery Pressure
Alarm
LO SUPPLY VOLTS P
Low Voltage Supply
Pre-Alarm
LOAD TAKEOVER
Load Takeover
Status
LOGIC OUPUT A
Logic Output
Alarm
LOGIC OUPUT P
Logic Output
Pre-Alarm
LOSS OF VOLT
Voltage Sensing Fail
Status
LOSS OF VOLT A
Voltage Sensing Fail
Alarm
LOSS OF VOLT P
Voltage Sensing Fail
Pre-Alarm
LOSS REM COMS P
Loss of Remote Module Communication
Pre-Alarm
LOST ECU COMM A
Loss of ECU Communication
Alarm
LOST ECU COMM P
Loss of ECU Communication
Pre-Alarm
LOW BATT VOLT P
Low Battery Voltage
Pre-Alarm
LOW CHARGE AIR PRESS P
Low Charge Air Pressure
Pre-Alarm
LOW COOL LEVEL A
Low Coolant Level
Alarm
LOW COOL LEVEL P
Low Coolant Level
Pre-Alarm
LOW COOL TMP A
Low Coolant Temperature
Alarm
LOW COOL TMP P
Low Coolant Temperature
Pre-Alarm
LOW COOLANT LEVEL P
Low Coolant Level
Pre-Alarm
LOW FUEL DELIV PRESS P
Low Fuel Delivery Pressure
Pre-Alarm
LOW FUEL LEVEL A
Low Fuel Level
Alarm
LOW FUEL LEVEL P
Low Fuel Level
Pre-Alarm
LOW FUEL RAIL PRESS P
Low Fuel Rail Pressure
Pre-Alarm
LOW OIL PRES A
Low Oil Pressure
Alarm
LOW OIL PRES P
Low Oil Pressure
Pre-Alarm
LOW OIL PRESSURE A
Low Oil Pressure
Alarm
LOW OIL PRESSURE P
Low Oil Pressure
Pre-Alarm
LOW STRG TANK LEVEL P
Low Storage Tank Level
Pre-Alarm
MAINS FAIL TEST
Mains Fail Test
Status
MAINT INTERVAL P
Maintenance Interval
Pre-Alarm
MF TRANSFER
Mains Fail Transfer Complete
Status
MF TRANSFER FAIL
Mains Fail Transfer Fail
Status
MN BKR CL FL P
Mains Breaker Fail to Close
Pre-Alarm
MN BKR OP FL P
Mains Breaker Fail to Open
Pre-Alarm
MPU FAIL P
Magnetic Pickup Fail
Pre-Alarm
Event Recording
DGC-2020ES