Remote display panel (optional) – Basler Electric DGC-2020ES User Manual
Page 32
24
9469200990 Rev C
6.
Phase Toggle Delay - Set the phase toggle delay to a nonzero value if automatic scrolling
through the phase information in the standard overview screen on the front panel is desired. If it is
left at zero, scrolling through phase information is accomplished using the up and down arrow
buttons.
7.
Initializing Message 1 - This parameter defines the first line of text that appears on the front panel
of the DGC-2020ES as it is going through its power up and initializing sequence.
8.
Initializing Message 2 - This parameter defines the second line of text that appears on the front
panel of the DGC-2020ES as it is going through its power up and initializing sequence.
Figure 7. Settings Explorer, General Settings, Front Panel HMI Screen
Remote Display Panel (optional)
Applications that require remote annunciation can use Basler Electric’s Remote Display Panel. This
device provides remote indication of many pre-alarm and alarm conditions.
The following pre-alarm conditions are indicated by LEDs on the Remote Display Panel:
•
High coolant temperature
•
Low coolant temperature
•
Low oil pressure
•
Low fuel level
∗
•
Weak battery
•
Battery overvoltage†
•
Battery charger failure
∗†
The following alarm conditions are indicated by LEDs and an audible alarm on the Remote Display Panel:
•
Low coolant level
∗
•
High coolant temperature
•
Low oil pressure
•
Overcrank
•
Overspeed
•
Emergency stop activated
•
Fuel leak/Sender failure
∗†
•
Sender failure†
∗ This can be configured in the DGC-2020ES as None, Alarm, or Pre-alarm. See the Contact Inputs
chapter for more information. The LED on the Remote Display Panel illuminates when the input that is
Controls and Indicators
DGC-2020ES