Mains fail transfer status – Basler Electric DGC-2020ES User Manual
Page 77
9469200990 Rev C
69
Switches 1 through 4
Each of these switches can be opened or closed by clicking on the Open or Close buttons. The switch is
closed when the corresponding indicator is red. These buttons control the virtual inputs found in
BESTlogicPlus Programmable Logic. The number of the switch corresponds to the number of the virtual
input it controls. See the BESTlogicPlus chapter for more information.
Figure 38. Metering Explorer, Control Screen
Mains Fail Transfer Status
The Mains Fail Transfer Status screen (Figure 39) displays the Mains Fail Transfer State and any timers
relevant to the mains fail transfer process. These parameters are listed below.
Mains Fail Transfer State: The different mains fail transfer states are described below.
Power From Mains: Power is being supplied to the load from the mains bus.
Transfer Timer Active: Transfer Delay timer is actively counting.
Transferring to Gens: Load is being transferred to the generator bus.
Power From Gens: Power is being supplied to the load from the generator bus.
Return Timer Active: Return Delay timer is actively counting.
Transferring to Mains: Load is being transferred to the mains bus.
Disabled: DGC-2020ES is in the OFF or RUN operating mode or in the alarm state.
Remaining Transfer Delay: Displays the current timer value in seconds.
Remaining Return Delay: Displays the current timer value in seconds.
DGC-2020ES
Metering