Basler Electric DGC-2020ES User Manual
Page 15
9469200990 Rev C
7
the next space. Once the password has been entered, press the Edit key again to login. A LOGOUT
selection now appears in the list of SETTINGS. To logout, navigate to SETTINGS > LOGOUT and press
the Edit key. The LOGOUT selection is removed from the SETTINGS list.
If communication access is active through the USB port, the front panel will display REMOTE COMMS,
FRONT PANEL IS READ ONLY, and the summary screen. This informs the user that the front panel can
only be used for viewing metering data and settings information. USB port access must be ended before
modifying settings through the front panel.
If a front-panel key is not pressed for more than 15 minutes, the user is automatically logged out.
Summary Screen and Configurable Metering
The summary screen can be set to standard or scrolling. When set to standard, only the following
parameters are displayed:
•
VOLT
∗
•
AMP
∗
•
PH
∗
•
Hz
•
OIL
•
FUEL
•
TEMP
•
BATT
∗ When set to standard, individual phase information can be automatically toggled at a rate set by the
Phase Toggle Delay setting. Navigate to the SETTINGS > GENERAL SETTINGS > FRONT PANEL HMI
screen and edit PH TOG DELAY. When the Phase Toggle Delay is set to zero, information for each
phase is obtained by pressing the Up or Down arrow keys on the front panel HMI. When it is set to a
number other than zero, the display will toggle through the phases automatically at the rate specified by
the Phase Toggle Delay Setting.
When the summary screen is set to scrolling, you can select/configure the metering values that are
displayed. Up to 20 values can be displayed and these values will scroll at a delay time specified by the
user. To select a standard or scrolling summary, navigate to the SETTINGS > GENERAL SETTINGS >
FRONT PANEL HMI screen and edit the SUMMARY VIEW. The SCROLL DELAY setting is also found on
this screen.
To select the scrolling values, navigate to the SETTINGS > GENERAL SETTINGS > FRONT PANEL HMI
screen and edit the CONFIGURABLE METERING. The following parameters may be placed in the
scrolling summary:
•
BATT V
•
BLANK (Shows nothing on this line)
•
BOOST PRESS
•
BUS Hz
•
BUS VAB
•
BUS VBC
•
BUS VCA
•
CHRG AIR TMP
•
COOLANT PRESS
•
DEF1 %
•
DEF2 %
•
ENGINE % LOAD
•
ENG INTCLR TEMP
•
ENG OIL TEMP
•
FUEL
•
FUEL DELV P
•
FUEL RATE
•
FUEL TEMP
•
GEN VBN
•
GEN VCA
•
GEN VCN
•
INJ RAIL PRS
•
INTAK MNFLD TMP
•
kVA A
•
kVA B
•
kVA C
•
kVA TOT
•
kvar A
•
kvar B
•
kvar C
•
kvar TOTAL
•
kW A
•
kW B
•
kW C
•
kW LD%
•
kWh
•
kW TOT
DGC-2020ES
Controls and Indicators