Figure 76. Settings Explorer, CAN Bus, ECU Setup
Remote Display Panel (optional)
Applications that require remote annunciation can use Basler Electric’s Remote Display Panel. This
device provides remote indication of many pre-alarm and alarm conditions.
Remote Display Panel connections are made at 10 (RDP TxD–), 11 (RDP TxD+), 17 (BATT–), and 18
(BATT+).
The following pre-alarm conditions are indicated by LEDs on the Remote Display Panel:
•
High coolant temperature
•
Low coolant temperature
•
Low oil pressure
•
Low fuel level
∗
•
Weak battery
•
Battery overvoltage†
•
Battery charger failure
∗†
The following alarm conditions are indicated by LEDs and an audible alarm on the Remote Display Panel:
•
Low coolant level
∗
•
High coolant temperature
•
Low oil pressure
•
Overcrank
•
Overspeed
•
Emergency stop activated
•
Fuel leak/Sender failure
∗†
•
Sender failure†
∗ This can be configured in the DGC-2020ES as None, Alarm, or Pre-alarm. See the Contact Inputs
chapter for more information. The LED on the Remote Display Panel illuminates when the input that is
assigned to the programmable function is closed, whether the function is configured as None, Alarm, or
Pre-alarm.
† This LED can be reprogrammed in the DGC-2020ES to suit the needs of a particular application. The
condition listed above is annunciated by default.
DGC-2020ES
Communication