Cable lengths must not exceed twenty-five (25) feet. For lengths greater than 25 feet, calculate
the voltage drop from the following formula:

2 X DISTANCE X CABLE RESISTANCE PER FT. X CURRENT = VOLT DROP

Table 3-2: Suggested Output Wiring Sizes *

Load Current

Wire Gauge (US)

Circular Mils

(kcmils)

Metric (mm2)

65 AMPS

6 AWG

26.24

13.3

130 AMPS

4 AWG

41.74

21.1

Note: Use high temperature rated wire. Always consult the National Electrical Code

and/or local code regulations for proper rating and size of wire cabling prior to
installation.