beautypg.com

AMETEK MX15 Series User Manual

Page 25

background image

User Manual

– Rev M

California Instruments

MX15

25

2.6.2

-XV Option Specifications

Consult factory for -XV option specifications.

2.6.3

-HF Option Specifications

The -HF option extends the maximum available output frequency from 819 Hz to 900 Hz. Some
restrictions are in effect at this increased output frequency level.

All other specifications of the MX15 system remain unchanged if this option is installed except as
noted in the table below.

-HF Option:

Frequency

Range:

-HF option:

16 Hz - 900 Hz

Resolution:

0.01 Hz

< from 16.00 to 81.92 Hz

0.1 Hz

> from 82.0 to 819.2 Hz

1 Hz

> from 820 to 900 Hz

Accuracy:

± 0.01 %

Phase

Accuracy:

16 - 100 Hz:

< 1.5°

100 - 500 Hz:

< 2°

500

– 819 Hz:

< 4°

819

– 900 Hz:

< 5°

Voltage

High Voltage Range

Maximum voltage at 900 Hz is 290 Vrms
Maximum frequency at 300 Vrms is 875 Hz
See Figure 2-7

Low Voltage Range

Maximum voltage at 900 Hz is 145 Vrms
Maximum frequency at 150 Vrms is 875 Hz
See Figure 2-8.

-HV Voltage Range

Maximum voltage at 900 Hz is 386 Vrms
Maximum frequency at 400 Vrms is 875 Hz .

Note: If the voltage or frequency settings shown here are exceeded for
any length of time (> 1 sec), the MX may shut down generating an over
temperature fault to protect itself.