Extended Open Time - Used in connection with access groups, it allows certain access groups an
extended number of seconds a door can be held open for entrance or exit before the controller generates
a door held alarm.
First Person In - The First Person In (FPI) function allows an operator to determine if a door should be
automatically unlocked when the unlock/lock time zone begins or if the door should not automatically
unlock until after a person presenting a valid card arrives. This feature is used whenever there is a
concern that employees may be delayed in arriving to a secured site (perhaps due to inclement weather).
Request To Exit (RTE) 1 - The Request to Exit (RTE) input accepts a signal from a normally open
input device such as a push button. There are four door configuration options for RTE 1: Not Used,
Momentary Unlock, Continuous Unlock, and Do Not Unlock.
•
Not Used – There is no request to exit function at all. Exit is not allowed through that door via
RTE.
•
Momentary Unlock – The request to exit is recorded, the door held open timer starts, and the
door unlock relay unlocks the door to allow exit.
•
Continuous Unlock (CRTE) – (This feature is not supported at this time.) The request to exit is
recorded and any assigned Auto Unlock/Lock (AUL) time zone is Suspended for a given door.
Then, while the CRTE input is active, the door is unlocked. When CRTE becomes inactive, the
door will assume its AUL time zone configuration state.
•
Do Not Unlock – The request to exit is recorded and the door held open timer starts, but the
door must manually be opened for exit (typically the door has a manual door strike, crash bar
or similar device).
Request To Exit (RTE) 2 - Not supported at this time.
Door Lock Relay Active - Select relay to energize or de-energize if this alarm condition occurs.
Door Forced Relay Active - Select relay to energize or de-energize if this alarm condition occurs.
Door Held Relay Active - Select relay to energize or de-energize if this alarm condition occurs.
Alarm Shunt Relay Active - Select relay to energize or de-energize if this alarm condition occurs.
Door Switch Contact Type - Select normally open or normally closed.
Door Switch Circuit Type - Select the supervised state of the switch.
Request To Exit 1 Contact Type - Select normally open or normally closed.
Request To Exit 1 Input Circuit Type - Select the supervised state of the switch.
Request To Exit 2 Contact Type - Select normally open or normally closed.
Request To Exit 2 Input Circuit Type - Select the supervised state of the switch.
Latch Integrity Contact Type - Not supported at this time.
Latch Integrity Circuit Type - Not supported at this time.