Electronic thermal protection, Cr-.pr, Electronic thermal protection 0 – Toshiba Tosvert VF-A5 User Manual

Page 79: U r . r, L- i

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

u r .

r

(Protection Parameters)

0

1 n

L- I

i

Electronic thermal protection @

D L O

OL selection

S t L /

S t C 1

Stall protection

The OL selection parameter| QL H can be set as follows,

0 L n

setting value

Function

0

Standard

+

1

Soft-stall ON

+ 3

Motor overload

( Q L f i t

) trip OFF

Note) When 3 i s selected, both the + J and + ^functions are enabled.

* The motor overload trip can be enabled/disabled with OL i l , but the inverter overload trip is always

enabled.

Soft-stall function:

When the inverter detects an overload, the output frequency will automatically be lowered before the motor

overload trips { O L f i t )• The load current will stabilize at the reduced frequency, and operation will

continue without tripping.

This function is applicable to variable torque loads such as fans, pumps and blowers, which exhibit the

characteristic that when the operating speed decreases, the load current also decreases.

■ k Do not use soft-stall on constant torque loads (loads with a constant load current regardless of speed).

Inverter overload protection curve

t

Time

: This protection curve cannot be changed or turned off

with parameter settings. This is built-in to protect the

inverter unit. If the inverter overload trip (

O L / n )

C r . P r

activates,

lower

|

5h

L

f

1

in

Cr.Pr

(stall

protection level (current limit level adjustment)), and

increase the acceleration time ( I PCC I I or

R C E 3 ) ^0 decrease the chances of this occuring.

100%: Inverter rated current

llflJi 150%

Output current