(2) Settings monitor mode adjustment function (Parameter group C r . R f l )

This function is used to adjust the scale when an analog meter is installed to monitor the output

frequency or current.

This adjustment is done in the same manner as the parameter setting and display function, except that

the meter indicator amplitude changes, instead of the LED display, when the

A V

keys are

pressed. The value indicated by the meter is adjusted to match the LED display, and is adjusted while

running.

If C r-.R n is not displayed, set b L n d (blind function) in G r . U t . (Refer to page 50.)

Example of FM (Frequency Meter) adjustment

Key operation

Example display

Explanation

SD.0

Standard monitor mode (operating frequency is displayed)

PRC

:Cr.u

Change to settings monitor mode.

A

V

i C r . n n

Select 0 r - . R n . (The group name will change when

A V

are

pressed.) UiiiF : H F S —-— O t t

ENTE

n

i C r . R n

Set the group. The first parameter name will be displayed.

- * :

f r

5

l

A

\ /

:

f r

5

l

Select the parameter name. (The parameter name will change

z_\

V

when A

V

are pressed.) F 0 5 L R : ^ R 5 L AiR 0

ENTE Ft

F R 5 L

Set the parameter. The parameter setting will be displayed.

: a

Select the FM terminal function with theA

V

keys to output the

A

V

:

f r s l

pre-compensation reference frequency.

ENTE

R

0

Set the data

V

:

f r

Display the next parameter name.

:

6

0.0

Set the parameter. The FM adjustment mode will be entered.

(The adjustment value will be displayed.)

A

V

:

6 0.0

Adjust the frequency meter value with the

A V

keys. (The

display will blink)

1

- (The LED display will not change, but the meter indicator

I

wiil move.)

1

- (Adjust with the ^

V

keys until the LED display and meter

i

value are the same.)

The adjustment value will be stored in inverter memory. (The

ENTE

R

G 0 . 0

blinking will stop.)

PRG

6 0.0

Move to standard monitor mode (frequency display).

Note) When DC voltage is selected for | F 0 5 L

or

R n 5 L and the main circuit power is turned

OFF ( n D F F status), the FM (AM) output will not be 0, but instead will show a slight output.