Safety Precautions

This inverter is for driving a 3-phase motor, and must not be used for other applications.

[I] Always observe the following items to prevent electrical shock.

1. Do not touch charged parts such as the terminal block while the CHARGE lamp is lit. A charge will still

be present in the electrolytic capacitors, and therefore, touching these areas may result in an electrical

shock. Always turn the inverter’s input power off before wiring the motor terminals. Walt at least five

minutes after the "CHARGE' lamp has gone out, and then confirm that the capacitors have fully

discharged by using a tester, etc., that can measure high-voltage DC.

Ijili->/7

'I

1111

/

llll

L=y

Control section

High voltage area

2. Do not touch or insert a rod or any other item into the

inverter while power is applied (there are high voltage areas

on the PCB), as this may lead to electrical shock or inverter

damage.

(When operating with the cover removed, charged areas will

be exposed, so always install the unit inside a panel so that

it cannot be easily touched.)

Never attempt to modify the inverter unit.

3. Ground the unit’s G/E terminal and the motor. (Electric

shock may occur due to leakage currents.)

[n] Retry function

(W/hen cover is removed)

1. This inverter has a "retry function" that automatically resets the unit when a fault trip occurs. Observe the

following points when this function is selected.

Even if the inverter has fault tripped, take care to not get caught in the motor or equipment. When the

"retry function" is selected, the inverter will automatically start after the designated time. (Refer to page

78.)

Take special care when an overload trip occurs, as the "retry function" may activate after a delay of up

to 5min.

[m] Observe the following points to prevent fire.

1. Confirm the inverter’s rating nameplate, and connect a 3-phase input power source within the rated range

to the RA.1, S/L2, and TA- 3 power source terminals.

If an Incorrectly-rated power source is connected to the inverter, such as when a 400V power source is

connected to a 200V inverter, the inverter’s internal components may explode.

2. No fuse is contained in the inverter, so instail a suitable non-fuse breaker (MCCB) on the inverter’s input

power source.

(Refer to Table 5-1 on page 14 for Examples of selecting equipment for wiring.)