beautypg.com

2 cautions regarding the inverter – Toshiba Tosvert VF-A5 User Manual

Page 12

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Braking during power off:

Loads that generate a

negative torque:

Motors with brakes:

The inverter will enter the coast-stop state when the power source is

turned off. The motor will therefore not stop immediately. To stop the

motor immediately, install an auxiliary brake unit. Dynamic braking

units and mechanical braking units are available, so select one that

suits your specific appiication.

The overvoltage protection or overcurrent protection may function and

trip the inverter when used with loads that generate a negative torque,

in this case, a braking resistor that meets the load condition must be

instalied.

If a motor with a brake is directly connected to the inverter, the

voltage when the motor is started will be low, which may result in the

brake not being released. In this case, separately wire the brake

circuit and motor main circuit. In addition, there is a delay in the time

to when the inverter output stops if the inverter’s ST to CC control

terminal connection is released, so use of the circuit configuration in

Fig. 4-1 is recommended.

In Fig. (a), the brake power is turned ON and OFF via MC2 and MC3.

If a circuit configuration as shown in the drawing is not used, a bound

current may flow during braking and may cause an overcurrent trip.

The brake power can also be turned ON and OFF using the low-

speed signal LOW as shown in Fig. (b).

(Non-excited brake)

Fig.4.1 Circuit configuration for motor with brake

In some cases, such as in hoist applications, turning the brake ON and

OFF by using low-speed detection (LOW terminal function) may be better,

so contact your dealer for further details.

4.2 Cautions Regarding the inverter

Inverter’s overcurrent

protection:

Overcurrent protection is used as the VF-A5 inverter’s protection

function, and the current setting level is set to match the largest

applicable motor. Therefore, when operating a motor that is smaller

than the inverter capacity, the overcurrent level and electronic thermal

protection parameters must be readjusted. (Refer to pages 72, 73.)