ESfcP in Cr.Pf- settings: D

I

Coast-stop
Decelerated stop
Emergency DC injection braking stop
If E is selected, also set the DC injection current

d b C and ESTOP DC injection time E d b t

* If DC braking is not required during normal stopping when

braking stop) is selected, set the DC braking time jcf b fc

ESfcP = E (emergency DC injection

to О .

Caution

The emergency stop command forcibly stops the motor with the inverter unit key operation even if the
command mode is not set to panel operation mode. This command cannot be prohibited with the

command mode selection. When executed, the emergency stop will be regarded as a trip and will be
recorded as a past fault.

7.4.7 Fault Reset

Remove the trip cause before resetting an inverter that has tripped due to a failure or other fault. The

inverter will trip again if the cause is not removed.

Reset the tripped state with one of the following methods:

Reset

(1) Turn off the power (until the LED display goes out) Note 1)
(2)

External signal (short circuit between control terminals RES-CC)

(3)

Panel operation

Resetting with the panel is performed by the following process.

Note 1)

Refer to

________ C r - . P r -

t г C L I (page 80).

STOP/RESET and confirm that C L г is displayed.

1.

Press

2.

Press STOP/RESET again, and if the trip cause has been removed, the inverter will be reset.

* For the following overload trips, the inverter cannot be reset with an external signal or with the panel

during the required cooling time.

: inverter overload

: motor overload

: dynamic braking resistor overload

DL I n

D L P b

DL

The standard cooling time settings are as follow:

: Approx. 1 minute after trip

: Approx. 5 minutes after trip

: Approx. 30 seconds after trip

DL I n

DL Dfc

DL

Caution

To reset immediately due to an emergency, the power can be turned off to reset the inverter, but if
this method is used frequently, the inverter or motor may be damaged.

-