Table 5.1: Examples of selecting equipment for wiring

Appncabfe

motor

m

Inverter

Non-fuse breaker

(MCC8)

Magnetic

contactor (MC)

Overload relay

Th-Ry

Model

Rated

current

(A)

Toshiba

model

Rated

current

(A)

Toshiba

model

(Note 1)

cunvnt value

_ w

{Reference

vfeue]

Toshiba

model

0.4

-2004P

5

SS30

12

C12A

2.3

T11A

0.75

-2007P

10

SS30

12

C12A

4.2

T11A

1.5

-2015P

15

SS30

12

C12A

6.6

T11A

2.2

-2022P

20

SS30

12

C12A

9.3

Til A

3.7

-2037P

30

SS30

18

C20A

15

T20A

5.5

-2055P

50

ESSO

35

C35A

22

T35A

7.5

-2075P

60

EH100

50

C50A

28

T35A

11

-211 OP

100

EH100

65

C65A

43

T65A

15

-2150P

125

EH225

80

C80A

57

T65A

18.5

-2185P

125

EH225

93

C100A

70

T80A

22

-2220P

150

EH225

93

C100A

85

T125A

30

-2300P

200

EH225

180

C180A

108

T125A

37

-2370P

225

EH225

180

C180A

138

T150A

45

-2450P

250

EH400

220

C220A

162

T180A

55

-2550P

250

EH400

220

C220A

198

T220A

75

-2750P

500

SH600

300

C300A

3.6

T400A

0.75

-4007P

5

SS30

9

C12A

2.3

Til A

1.5

-4015P

10

SS30

9

C12A

3.6

T11A

2.2

-4022P

10

SS30

9

C12A

5.0

Til A

3.7

-4037P

15

SS30

9

C12A

8

T11A

5.5

-4055P

30

SS30

17

C20A

11

T20A

7.5

-4075P

30

SS30

17

C25A

15

T20A

11

-4110P

50

ESSO

33

C35A

22

T35A

15

-4150P

60

EH100

48

C50A

28

T35A

18.5

-4185P

75

EH100

50

C50A

35

T35A

22

-4220P

100

EH100

50

C50A

43

T65A

30

-4300P

125

EH225

80

C80A

57

T65A

37

-4370P

125

EH225

93

C100A

70

T80A

45

-4450P

150

EH225

180

C180A

85

T125A

55

-4550P

175

EH225

180

C180A

108

T125A

75

-4750P

225

EH225

220

C220A

138

T150A

Voltage

dass

Surge killer

Model

(Note^

Wire size

Main

ciicuit

(mm^

(Notes)

Control

dfcuit

(mm^

(Note 4)

Dynamic

braking

(mm®)

200V
class

2.0

Toshiba

model SS-2

or

Marcon

Bectronics

RFM2E224KD

2.0

2.0

2.0

0.75 or

larger

3.5

14

5.5

14

22

8.0

38

38

22

60

100

100

60

100

100x2

400V
class

2.0

Model SS-2

or

Marcon

Bectronics

RFM2H104KD

(400V system)

(Note 6)

2.0

2.0

2.0

0.75 or

larger

3.5

5.5

2.0

3.5

14

22

8.0

38

38

38

22

60

100

(Note 1) When selecting a magnetic contactor (MC) with 2a auxiliary contacts and using the auxiliary contacts for the control circuit,

parallel the 2a contacts to improve contact reliability.

(Note 2) Install a surge killer on the magnetic contactor or relay exciting coil.
(Note 3) The wire sizes for the input side R, S, T and output side U, V, W are shown. These sizes apply only when the wiring length is

less than 30m. Increase the wire sizes when the length exceeds 30m.

(Note 4) Use shielded wire.
(Note ^ Use a wire size 3.5mm® or more for the grounding wire.