Upper limit/lower limit frequencies

Related parameters

Upper limit frequency

U L

L L

Lower limit frequency

The upper limit frequency U L sets the upper limit of the output frequency, and the lower limit frequency

L

l

' I sets the lower limit of the output frequency.

The upper limit frequency can be set between 0 and the max. frequency.

The lower limit frequency can be set between 0 and the upper limit frequency.

Output frequency H

z

Output frequency Hz

0

Frequency setting signal

* A frequency exceeding

U L will not be output.

* The output frequency cannot

be set below

l

L

* The operating frequency can only be set within the range of the upper limit frequency and lower limit

frequency when set from the panel. An error display ( H I S 0.0 alternately displayed) will occur if

an attempt is made to set the frequency from the panel above 50Hz when the upper limit frequency is set to

50Hz.

d I S г

Reverse operation disable selection

This is used to prevent reverse run problems which may occur if an incorrect start signal is input.

d 1 5 г setting value

Function

0

Reverse operation allowed

1

Reverse operation not allowed

* This applies to both panel and external control.

- 51