background image

5. Wiring Precautions

5.1 Connection to Main Circuit (Refer to page 11, Fig. 5.1.)

Observe the following precautions when making connections to the inverter.

Confirmation of power OFF:

Electrical shock prevention-

confirmation of charge

dissipation:

Confirmation of main circuit

connections:

Separation of power source

and motor wiring:

Separation of control and

main power supplies:

Always turn the primary power distribution panel switch OFF, and

confirm with a tester that a voltage is not present before beginning

wiring to the inverter.

Before changing the wiring, wait at least five minutes after the

•CHARGE“ lamp inside the inverter has gone out, and then confirm

that the capacitors have fully discharged by using a tester, etc., that

can measure high-voltage DC. The internal electrolytic capacitors are

charged, and there is a danger of electrical shock If the charged

areas are touched while the "CHARGE' lamp is on. Do not touch the

terminal block or remove the upper cover while the lamp is lit

The inverter will be damaged If the input power source is applied to

the motor terminals (U/T1, V/T2, W/T3). Always confirm the wiring for

the power source terminals (R/L1, S/L2, T/L3) and motor terminals

(U/T1, V/T2, W/T3) before turning the power on.

To prevent problems due to radio-frequency noise, etc., do not bundle

the wiring to the input power terminals (R/L1, S/L2, T/L3) and the

motor terminals (U/T1, V/T2, VJfTS) together.

In order to maintain the control power supply to display faults or to

operate the communication options while the main circuit power is

shut down, remove the two shorting bars (between R/L1-R0, S/L2-S0)

on the control power supply terminal block. Connect the control

power to a power source that is separate from the main circuit supply.

5.2 Connection of Control Signals

Observe the following points when making control signal connections.

Rating of relay contacts:

Power wiring for control

circuit:

Control wiring wire sizes:

Isolation from main circuit:

Use a relay intended for use with micro-current (min. applicable load

rating less than 4mA-24V.), and install a surge killer on the relay’s

exciting coil.

Use shielded wiring or twisted-pair wiring for the control circuit, and

separate the wiring from the main circuit wiring.

The following wiring sizes for the control circuit are recommended.

Frequency setting signal input, frequency meter, ammeter: shielded

wire that is 0.3mm® or larger

Other signals: Vinyl-insulated wire that is 0.75mm® or larger

All control terminals other than FLA, FLB and FLC are connected to

Internal electronic circuits, so input signals must always be electrically

isolated from the main circuit.

9

-