____Output terminal selections ®
The functions for the output terminals RCH (
0 f c 0
). LOW ( O b I ) , F L ( 0 b
E
) and OUT
( O t 3
) can be
selected from 62 types of signals according to the data in the following table.
* The output terminal block normally has three contact points, but by adding the expansion terminal block PCB
(optional) the output terminal OUT (0 fc
3
) can be added, for a total of four contact points.
Setting
value
Function
Setting
value
Function
0
LL (Frequency lower limit)
3 3
Executing emergency stop
1
/LL (opposite of LL)
3 3
/Executing emergency stop
3
UL (Frequency upper limit)
3 H
Executing retry
3
AJL (opposite of UL)
3 5
/Executing retry
H
Low speed signal
3 E
Pattern run switching output
5
/Low speed signal
3 1
/Pattern run switching output
B
Accel/decel complete
3 B
PID variation limit
1
/Accel/decel complete
3 3
/PID variation limit
B
Selected speed reach signal
H O
Run/stop
3
/Selected speed reach signal
H 1
/Run/stop
1 0
Fault FL
H 3
Severe fault (OCA, OCL, open phase.
1 1
/Fault FL
output error, EF)
I P
Fault occurrence other than EF or OCL
H 3
/Severe fault (OCA, OCL, open phase.
1 3
/Fault occurrence other than EF or OCL
output error, EF)
I H
Overcurrent pre-alarm
H H
Non-severe fault (OL, OC1, OC2, OC3, OP)
I B
/Overcurrent pre-alarm
H 5
/Non-severe fault
(OL, OC1, OC2, OC3, OP)
I E
Inverter overload pre-alarm
H E
Commercial power/lNV switching output 1
1 1
/Inverter overload pre-alarm
H I
/Commercial power/INV switching output 1
I B
Motor overload pre-alarm
H B
Commercial power/INV switching output 2
1 9
/Motor overload pre-alarm
4 9
/Commercial power/INV switching output 2
3 0
Overheat pre-alarm
5 0
FAN ON/OFF
3 1
/Overheat pre-alarm
5 1
/FAN ON/OFF
3 3
Overvoltage pre-alarm
5 3
Executing JOG
3 3
/Overvoltage pre-alarm
5 3
/Executing JOG
3 H
Undervoitage alarm
5 4
Terminal block operation command mode
3 5
/Undervoltage alarm
5 5
/Terminal block operation command mode
3 E
Undercurrent alarm
5 5
Cumulative timer alarm
3 1
/Undercurrent alarm
5 4
/Cumulative timer alarm
3 B
Overtorque alarm
5 B
Communication error alarm
3 9 >
/Overtorque alarm
5 9
/Communication error alarm
3 0
Braking resistor overload pre-alarm
K n
F/R
3
1
/Braking resistor overload pre-alarm
O
U
E 1
/F/R
Note) When the expansion terminal block PCB (optional) with 3 relay outputs is used, do not connect any
other devices to the standard RCH or LOW terminals.
The alarm and pre-alarm output signals always output the current inverter status, so that when the inverter
returns to its normal status, so will the output signals.