O b o 0 t 3, Output terminal selections – Toshiba Tosvert VF-A5 User Manual

Page 63

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

u r

.

5 tz 0*6'’'^'^^’ Selection Parameters)

O b O

0 t 3

____Output terminal selections ®

The functions for the output terminals RCH (

0 f c 0

). LOW ( O b I ) , F L ( 0 b

E

) and OUT

( O t 3

) can be

selected from 62 types of signals according to the data in the following table.

* The output terminal block normally has three contact points, but by adding the expansion terminal block PCB

(optional) the output terminal OUT (0 fc

3

) can be added, for a total of four contact points.

Setting

value

Function

Setting

value

Function

0

LL (Frequency lower limit)

3 3

Executing emergency stop

1

/LL (opposite of LL)

3 3

/Executing emergency stop

3

UL (Frequency upper limit)

3 H

Executing retry

3

AJL (opposite of UL)

3 5

/Executing retry

H

Low speed signal

3 E

Pattern run switching output

5

/Low speed signal

3 1

/Pattern run switching output

B

Accel/decel complete

3 B

PID variation limit

1

/Accel/decel complete

3 3

/PID variation limit

B

Selected speed reach signal

H O

Run/stop

3

/Selected speed reach signal

H 1

/Run/stop

1 0

Fault FL

H 3

Severe fault (OCA, OCL, open phase.

1 1

/Fault FL

output error, EF)

I P

Fault occurrence other than EF or OCL

H 3

/Severe fault (OCA, OCL, open phase.

1 3

/Fault occurrence other than EF or OCL

output error, EF)

I H

Overcurrent pre-alarm

H H

Non-severe fault (OL, OC1, OC2, OC3, OP)

I B

/Overcurrent pre-alarm

H 5

/Non-severe fault

(OL, OC1, OC2, OC3, OP)

I E

Inverter overload pre-alarm

H E

Commercial power/lNV switching output 1

1 1

/Inverter overload pre-alarm

H I

/Commercial power/INV switching output 1

I B

Motor overload pre-alarm

H B

Commercial power/INV switching output 2

1 9

/Motor overload pre-alarm

4 9

/Commercial power/INV switching output 2

3 0

Overheat pre-alarm

5 0

FAN ON/OFF

3 1

/Overheat pre-alarm

5 1

/FAN ON/OFF

3 3

Overvoltage pre-alarm

5 3

Executing JOG

3 3

/Overvoltage pre-alarm

5 3

/Executing JOG

3 H

Undervoitage alarm

5 4

Terminal block operation command mode

3 5

/Undervoltage alarm

5 5

/Terminal block operation command mode

3 E

Undercurrent alarm

5 5

Cumulative timer alarm

3 1

/Undercurrent alarm

5 4

/Cumulative timer alarm

3 B

Overtorque alarm

5 B

Communication error alarm

3 9 >

/Overtorque alarm

5 9

/Communication error alarm

3 0

Braking resistor overload pre-alarm

K n

F/R

3

1

/Braking resistor overload pre-alarm

O

U

E 1

/F/R

Note) When the expansion terminal block PCB (optional) with 3 relay outputs is used, do not connect any

other devices to the standard RCH or LOW terminals.

The alarm and pre-alarm output signals always output the current inverter status, so that when the inverter

returns to its normal status, so will the output signals.

- 57 -