background image

0 (Fundamental Parameters #2)

Function

Title

Adjustment range

Ftesolution

Default

Pago

Maximum voltage

frequency

#2

———--------- 1----

urLd

¡

25~400

■ 0.01/0.1 Hz

60.0

54

Maximum voltage #2

1 P 1

ulC 1

1

0~€00 (Note 1)

IV 200V system: 200V

400V system: 400V

54

Voltage boost #2

[

Ulbd

j

i

1

j

0-30

0.1%

Depends

on inverter

rating

54

Electronic thermal protection level #2

fcHr

-2

j

10-100%/A (Note 2)

1%/A

100.0

54

Stall protection #2

5

tcг

i

1

I

0; ON

1: OFF

0

54

54

0

Stall protection level #2
(current limit level
adjustment)

SfcLd i

1

1

1

I

10-215%/A

1%/A

150.0

Acceleration time #2

Deceleration time #2

I

d£Cd

!

1

j

0.1-6000/0.01-600.0

0.1-6000/0.01-600.0

0.1/0.01 S

0.1/0.01 S

Depends

on inverter

rating

46

Acc/dec pattern #2

sc^г

i

1

1

I

1

j

0: Linear

1: Self-adjusting

2: S-Pattern #1
3: S-Pattern #2

0

54

Acc/dec #1/#2 switching frequency

RddF i

0—max. frequency (FH)

0.1/0.01 Hz

0.0

52

r" O

r~

(Panel Control Parameters)

Function

Title

Adjustment range

Resolution

Default

Page

Fonward/reverse

Fr-

i

1

I

0: Reverse

1: Forward

1

Stop pattern selection

StPP !

1

]

0: Decelerated stop

1: Coast stop

0

Fundamental parameter switching

PtP

i

1

1

1: Fundamental parameters #1 (V/F#1)

2: Fundamental parameters #2 (V/F#2)

1

54

Acc/dec #1/#2 selection

Pdd !

1

1

1: Acc/dec #1

2: Acc/dec #2

1

52

Panel reset selection

P^£S 1

1

1

0: Ail possible

1: OL only (fault ignore #1)

2: OU OCl. OC2, OC3 only (fault ignore #2)

0

53

Panel feedback control

• PID
• Speed Feedback
• Drooping

PPbC

i

1

1

1

1

1

_____________ L_

0: ON (valid when panel operation is

selected)

1: OFF (invalid when panel operation

is selected)

0

53

Note 1) 200V system: Internally limited to 255V.

400V system: Internally limited to 510V.

Note 2) Parameters with note ’A‘ shown in the Adjustment Range and Resolution columns will be displayed

in either percent or Amps depending on the setting of dSPC in

and uGci* • in C<"F are valid only when ciLSL in Cf-.f" is set to ’ ? *.

-107 -