11.2 Other Fault Troubleshooting

Perform the following checks if other faults occur.

The motor does not
run.

Yes

No

Is the LED display lit?

Check the input
power and MCCB.

I

is the input power

correct?

E

Use a properiy-rated
power source.

(D is the CHARGE

Open the

Turn the power off.

r “*

lamp lit?

cover.

Wait for the CHARGE lamp to completely turn off. (Wait for five minutes after it has gone out.)
Turn on only the control power with the main circuit power turned off. (Refer to page 18.)

0

is 24Vdc being

output between

P24-CC?

Turn off the
control power.

Is FU1 on the terminal

block PCB intact?

P24 may be externally

short circuited.

® is the operating

Insert the

is the flat cable between

Check that the fiat cable

panel correctly

operating

the terminal block PCB

----- ^ is inserted in the correct

inserted in the

panel

and control PCB

direction.

connector?

correctly.

correctly inserted?

There is a fault in
the inverter.

Is

P D F F

displayed?

The main circuit power supply
voltage is insufficient. Check the

wiring from the input voltage or

DCL, etc. The input voltage can
be checked in status monitor

mode (refer to section 7.3.2).

Has the internal cover
holding the control PCB
been removed in the
past?

"I...............

There is a fault in the

inverter.

is

P O F F

displayed?

The control power voltage is insufficient.

Is the flat cable

connecting the control

PCB and main circuit
PCB or power supply
PCB correctly inserted?

Check that the fiat cable
is inserted in the correct
direction.

There is a fault in the
inverter.

is OFF displayed?

ST-CC is open. Close it.

Is a fault message

displayed? Refer to
page 121._________

Investigate and remove the cause of the fault. Then press

the 1 STOP/RESET1 key on the operating panel, and confirm

that C L I- is displayed. Then press C^OP/RESEf] again.

If

r t r - i J

and a fault display are

alternately displayed.

Retry is being executed. The retry function

can be stopped with the stop/emergency
stop operation or by turning the power off.

Is .'

O . D

displayed?

Is the "PANEL CONTROL" |-____ ,
LED lit?

Press the IPANEL/REMOT~El key.

Is the frequency set?

If one or all of the eight operating panel keys do not
function, refer to page 84, and set

Read Chapter 7, section 7.2 ‘Basic operation" again.

L----------------- --------- -----------------------------

--------------------------—------------------------------------------------- --------------------------- -____________ I