7.3.4 JOG Run Mode

This mode is used to run the inverter at low speeds, and especially allows short-time runs (inching) to be

done easily. The following explanation is for executing jog from the panel. When using terminal block

signals to execute jog, refer to the parameter explanation section for C . 5 F JOG

This mode is entered via the following procedure.

The JOG run frequency (| J 0 G |in G r-.S F) and JOG stop control ( J 5 t P in G r-.S F)

parameters must be set from settings monitor mode before entering this mode. (Refer to page 70.)

Key operation

Example display

Explanation

PRG

PRG

C r . U

:

f

JDG

Press the

PRG

key twice. The JOG mode will not be entered

if a different key sequence is pressed. ____________

key is pressed

PRG

The JOG mode will be entered when the

the second time only if panel control mode is selected and the

JOG run frequency setting value is not OHz. (Forward JOG)

If panel control mode is not selected or the JOG run frequency

is not set, operation will return to standard monitor mode

(frequency display) when the

PRG key is pressed the second

time.

V

JDG

Execute reverse JOG by pressing V •

Execute forward JOG by pressing A •

RUN

5 . 0

The JOG run frequency will continue to be output while the

RUN key is held down.

PRG

0 . 0

Standard monitor mode will be returned to when PRG is

pressed.

Note) If positioning is attempted in JOG run mode and the motor shaft does not smoothly stop at the

desired location, set the output short-circuit detection selection (

value to 0 (position sensing during JOG). (Refer to page 80.)

OCL 5 in O r . P r )setting