7.3.4 JOG Run Mode
This mode is used to run the inverter at low speeds, and especially allows short-time runs (inching) to be
done easily. The following explanation is for executing jog from the panel. When using terminal block
signals to execute jog, refer to the parameter explanation section for C . 5 F JOG
This mode is entered via the following procedure.
The JOG run frequency (| J 0 G |in G r-.S F) and JOG stop control ( J 5 t P in G r-.S F)
parameters must be set from settings monitor mode before entering this mode. (Refer to page 70.)
Key operation
Example display
Explanation
PRG
PRG
C r . U
:
f
JDG
Press the
PRG
key twice. The JOG mode will not be entered
if a different key sequence is pressed. ____________
key is pressed
PRG
The JOG mode will be entered when the
the second time only if panel control mode is selected and the
JOG run frequency setting value is not OHz. (Forward JOG)
If panel control mode is not selected or the JOG run frequency
is not set, operation will return to standard monitor mode
(frequency display) when the
PRG key is pressed the second
time.
V
JDG
Execute reverse JOG by pressing V •
Execute forward JOG by pressing A •
RUN
5 . 0
The JOG run frequency will continue to be output while the
RUN key is held down.
PRG
0 . 0
Standard monitor mode will be returned to when PRG is
pressed.
Note) If positioning is attempted in JOG run mode and the motor shaft does not smoothly stop at the
desired location, set the output short-circuit detection selection (
value to 0 (position sensing during JOG). (Refer to page 80.)
OCL 5 in O r . P r )setting
-39