Function
Titfe
Adjustment range
Resolution
Default
Page
Undervoltage trip selection
UP5L I
1
0: Trip disabled
1: Trip (during run)
—
0
80
Undervoltage detection time
UPt ¡
0~10
0.01 sec.
0.03
80
Low current detection selection
(output fault detection)
< < p 1
!
0: Trip disabied
1; Trip on detection
—
0
80
Low current detection level
L L P C j
0~100%/A
1%/A
0
80
Low current detection time
LLPfc
0~255
1 sec.
0
80
Output short-circuit detection
selection (OCL)
C C L S
!
1
1
0: Standard
-M: High-speed motor use
+2: Position sensing (during JCX3)
0
80
Overtorque trip selection
1
CfcSL 1
j
0: Trip disabled
1; Trip enabled
—
0
80
Overtorque trip level
OtL i
0~200%/A
1%/A
150
80
Fault trip saving
1
1
0; Cleared when powered OFF
1: Data retained when powered OFF
-
0
81
Cooling fan control selection
FRn i
1
1
0; Automatic (temperature detection)
1: Always ON
—
0
—
Cumulative run timer alarm setting
CJfc i
t
0.00~999.9
(1 = 100 hours)
0.02
(two hours)
175.0
35
r“ r^i
i j * “ . * « C (Motor Parameters)
Function
Title
Adjustment range
Resolution
Default
Page
Number of motor poles
ntP
j
2. 4, 6. 8. 10, 12, 14, 16
2
4
47
Motor rated capacity
ntz
1
1
1
j
0.1~75.0
0.1
kW
Depends
on inverter
rating
Motor type
ntt i
1
1
„ ........ -j_ .
0: Toshiba
standard motor
1: Toshiba VF motor
2: Other
—
0
1
2 |Rated voltage
j Rated frequency
rifcjLJ
^
•
flfcf ¡ •
90-600
0~-100
5V
2Hz
200/400
60
1
Rated RPM
1........ ...................... ....... . ........... flfcr ¡ .
0-9999
1 RPM
1710
n
* Auto-tuning
1
1
ntfco ¡ •
1
1
0: Auto-tuning disabled
1; Auto-tuning enabled
-
0
Load moment of inertia
rifc. SH i
1
1
1
i
0: Small (VerlOO/102)
1: Medium (Veri 10 standard)
2: Large
3: Very large
1