Gnxip

Hoist

Function

Trtle

Adjustment range

Resolution

Default

Re­

marks

Dynamic braking selection (DBR)

Pb i

t

1

1

I

0: No DBR

1: With DBR, no OLr detection

2: With DBR and OLr detection

Dep«ndt

on Inverter

ratlrig

Gr.Pr

Overvoltage stall protection

GPSS !

1

1

0: ON

1: OFF

0

Gr.Pr

DC injection starting frequency

Other j DC injection current

than j DC injection time

0 !

dbP j

0-120

0.1/0.01 Hz

0.0

Gr.Pr

dbC

I

dbb

j

*

0-100%/A
0-10

1%/A

0.1 sec.

0

0.0

Forward/reverse DC injection priority
control

1

dbSL 1

0: OFF

1: ON

-

1

Gr.Pr

Emergency stop selection

[

£ 5 b P j

1

............. j . . . .

0: Coast-stop

1; Decelerated stop

2: DC injection stop

0

Gr.Pr

1

2 I ESTOP DC injection time

Edbb j•

0—10 sec.

0.1 sec.

0.1

Motor overload protection level

bH^ ! j

10-100%/A

1%/A

100

Gr.Pr

OL reduction start-up frequency

CLP

0-30

0.1/0.01 Hz

30.0

Gr.Pr

OL selection

ril o

>

1

1

1

I

1

0: Standard

+

1: Soft-stall ON

+2: OLMt trip OFF

0

Gr.Pr

Stall protection

SbC ! 1

1
1

0: ON

1: OFF

10-215%/A

1%/A

0

150

Gr.Pr

0 j Stall protection level (current

¡limit level adjustment)

ShL • I

Output short-circuit detection
selection (OCL)

c i

1

1

1

I

0: Standard

-M; High-speed motor use
+2: Position sensing

(during JOG)

0

Gr.Pr

Fault trip saving

1

1

1

0; Cleared when powered OFF

1: Data retained when powered

OFF

0

Gr.Pr

FM terminal function selection

cr^ci 1

r*i

iDv-

1

1

t

1

1

0-13

Refer to the standard parameter

list for details.

0

Gr.AM

Frequency meter adjustment

PC

1

Gr.AM

AM terminal function selection

RGSL

i

1

1

I

0-13
Refer to the standard parameter

list for details.

3

Gr.AM

Ammeter adjustment

PC j

Gr.AM

Number of motor poles

GbP I

2, 4, 6, 8, 10, 12, 14, 16

2

4

Gr.Mt

Motor rated capacity

GbG j

0.1-75.0

0.1 kW

(Ncte 1)

Gr.Mt

Motor type

Gbb 1

1

1

0: Toshiba standard motor

1: Toshiba VF motor

2; Other

0

Gr.Mt

2 1 Rated voltage

1

i

C

jlj

• •

90-600

5V

200/400

j Rated frequency

GbP

0-400

2 Hz

60

»Rated RPM

\-

Gbi- j •

0-9999

1RPM

1710

1
¡Auto-tuning
1

1

Gbb<-» 1 *

1

1

0: Auto-tuning disabled

1: Auto-tuning enabled

-

0

Load moment of inertia

Gb. !H I

___________t -

0-3

-

1

Gr.Mt

(Note 1) Same as inverter capacity