Table 6.2.3. Control circuit terminal functions
Control circuit terminal functions are as shown below. The internal circuit diagrams for each terminal
are shown on page 22.
Terminal symbol
Terminal function
Internal
circuit
diagram
FLA, FLB, FLC
These are the multifunction programmable relay contact outputs (refer
to page 12). The contact ratings are 250Vac-2A (COS0=1), 30Vdc-1A,
250Vac-1A (COS0=O.4).
The standard function setting detects when the inverter protection
functions have operated.
When a protection function activates, FLA-FLC will close, and FLB-FLC
will open.
E
P24
24Vdc power output. (Max. 100mA)
F
RCH
This is a multifunction programmable open-collector output (refer to
page 57). (Max. SOmAdc)
The standard function setting activates this signal when completion of
deceleration or acceleration is detected.
G
LOW
This is a multifunction programmable open collector output (refer to
page 57). (Max. 50mAdc)
The standard function setting activates this signal when a low speed is
detected.
G
FP
This is a dedicated open-collector output. (Max. 50mAdc). Pulses that
are 48-, 96- or 360-times the output frequency are output according to
parameter settings.
The standard setting is for 48-times the output frequency.
H
FM
This is a multifunction programmable analog output (refer to page 89.)
The standard setting is the pre-compensation reference frequency.
When connecting a meter, use a ImAdc full-scale ammeter or 7.5Vdc-
1mA full-scale voltmeter.
1
AM
This is a multifunction programmable analog output (refer to page 89.)
The standard setting is the output current. When connecting a meter,
use a ImAdc full-scale ammeter or 7.5Vdc-1mA full-scale voltmeter.
1
PP
This is the power supply for reference frequency setting. (lOVdc)
Connect a 3kft potentiometer (a 1 to lOkQ potentiometer may also be
used).
J
RR
This is a multifunction programmable analog input.
The standard setting is a 0 to lOVdc input corresponding to a 0 to
80Hz frequency setting.
K
IV
This is a multifunction programmable analog input. Change between 0
to lOVdc (SW at V side) or 4 (0) to 20mAdc (SW at 1 side) via SW,
located under the ROM interface window. The standard setting is a 0 to
lOVdc input conresponding to a 0 to 80Hz frequency setting with the
switch at the V side.
L
RX
Tills is a multifunction programmable + ! - analog input. Change
between 0 and ±lOVdc (SW at 10V side) or 0 to ±5Vdc (SW at 5V
side) via SW, located under the ROM interface window. The standard
setting is a 0 to ±10Vdc input corresponding to a 0 to 80Hz
forward/reverse frequency setting with the switch at the 10V side.
M
CC
This is the control circuit common terminal.