Toshiba Tosvert VF-A5 User Manual
Page 26
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Terminal symbol
Terminal function
Internal
circuit
diagram
ST
■ 3
Q.
C
*—•
0
ro
c
0
0
CD
JD
CO
e
E
CO
O)
0
Q.
c
0
0
c
3
D
The standard setting is ‘run ready' with a short circuit between ST-
CC. The motor will coast-stop when opened. This can also be
used for interlocks. (Run ready/ coast-stop terminal)
0
F
The standard setting is forward run with a short circuit between F-
CC, and decelerated stop when opened. (ST-CC in ON condition)
0
R
The standard setting is reverse run with a short circuit between R-
CC, and decelerated stop when opened. (ST-CC in ON condition)
The motor will reverse run when both F-CC and R-CC are short
circuited.
0
SI
The standard setting is preset speed run with a short circuit
between S1-CC.
0
S2
The standard setting is preset speed run with a short circuit
between S2-CC.
0
S3
The standard setting is preset speed run with a short circuit
between S3-CC.
0
S4
The standard setting is preset speed run with a short circuit
between S4-CC.
0
RES
The standard setting is that the hold during operation of the
inverter protection functions is reset with a short circuit between
RES-CC.
Even if RES-CC Is short circuited while the inverter is operating
normally, the reset function will not activate.
0
-
20
-