Table 11-1 Fault displays, details, and remedies
Display
Details
Presumed causes
Remedies
Reference
page
П Р Э
Overvoltage during
constant speed run
• The input voltage fluctuated abnormally.
© The power source capacity is SOOkVA
or more.
® Power-factor improvement capacitors
went on-line/off-line.
® A device using thyristors is connected
to the same power line.
Try inserting an input AC reactor.
13
• The motor is rotating at a frequency
higher than the inverter output frequency
due to a force on the load, and is in a
regenerative state.
© There are multiple machanioaily-
coupled motors.
® The load undergoes piston-type cyclic
movement
Change the load so that a regenerative
state is not entered.
Install a dynamic braking resistor.
17
D L I n
Inverter overload
• Sudden motor acceleration was
attempted.
Decrease the acceleration time
[ Я С С 1 •
48
-
• The DC injection current (time) is set too
high Oong).
Decrease the DC injection current
1 cfb C 1 DC injection time
74, 75, 76
1
db fc 1 '
• Start was attempted on a rotating motor
after momentary power failure, etc.
Use auto-restart or regeneration power
ride-through control.
79
• The load is too large.
Increase the inverter rating.
90
DL ЛЬ
Motor overload
• V/f is incorrect
Check the V/f pattern setting.
45
• The motor is constrained.
Check the load equipment.
5
• Continuous running at low speeds.
• Motor is being operated in the overload
area.
Adjust I D
L
Г" i according to the
motor's overload handling characteristics
at low speeds.
72
DCr
Dynamic braking
resistor overcurrent
trip
• The motor decelerated suddenly.
Decrease the deceleration time
1
oLEL
l
•
48
O L r
Dynamic braking
resistor overload
• The DC injection current is too high.
Decrease the DC injection current
1 cf ЫГ 1 and DC injection time
74, 75, 76
trip
1 d b b 1 •
D H
Overheat
• The cooling fan is not working.
Check the cooling fan.
—
• The fan ventilation inlet is blocked.
• Another heat-generating device is located
nearby.
Check the inverter installation space.
Do not place heat-generating devices near
the inverter.
2
• The thermistor in the unit is dislocated.
Check the main circuit PCB CN6.
£
Emergency stop
• Motor was stopped during automatic run
or remote operation with the panel.
Reset.
43, 44
E E P 1
EEPROM fault
• An error occurred during writing of data
to the EEPROM.
Cycle power to the unit OFF/ON. If the
error persists, repair is required.
44
Е Е Р Б
Initial read fault
• Fault in the internal data.
Repair is required.
—
E r r SRAM fault
• Fault in the microcontroller RAM.
Repair is required.
—
E r г 3ROM fault
• Fault in the microcontroller ROM.
Repair is required.
E r г ЧCPU fault
• Fault in the microcontroller CPU.
Repair is required.
—
E r r S
Communication
• A fault occurred during communication
Check the communication device and
_
operating
command fault
operation.
wiring, etc.
Е г г Б
Gate array fault
• Fault in the main gate array.
Repair is required.
_
E r r !
Output current
detection device
fault
• Fault in the output current detection
device
Repair is required.
—
E r r ВOption PCB fault
• Fault in an option PCB.
Check the option PCB connections, etc.
* U E
Low current run
condition trip
• The output current dropped to the low
current detection level while running.
—
98
-