Table A-6: BMM (Burner Management Module) Fault Codes (Continued)

CODE DESCRIPTION EFFECT

CORRECTION

RESET

14

Return Sensor

fault

All burners

turned

OFF.

Check return sensor or

wiring.

AUTOMATIC

15

Maximum Δ-

temperature

protection. Flow

temperature -

Return

Temperature >

Water Δ-Temp

Protection + 50°F

All burners

turned OFF

and Pump

ON at

maximum

speed.

Check the system

installation.

AUTOMATIC - when

Δ-temperature < Water

Δ-Temp Protection.

16

Boiler Pipe is

frozen.

FlowSensor

temperature is

36°F or less.

Ignition is

inhibited.

Pump runs

for 5 min at

max speed.

Carefully defrost boiler

AUTOMATIC - when

FlowSensor is greater

than 41°F.

20

Flame signal

detected after

burner is OFF.

Ignition is

inhibited.

Disconnect gas valve wire

from BMM. If failure goes

away, check wiring or

change BMM. If failure

remains check or change

gas valve.

MANUAL - push reset

switch or cycle power.

22

No air flow at

burner after fan

started for 30

seconds.

Ignition

retry after

60 second

delay and

failure

remains

until we

have a

successful

burner

operation.

If fan is stopped, check

supply voltage and fan

wiring. If OK try another

fan. If still not working

change the BMM.

If fan is not stopped, check

the exhaust gas outlet for

blockage. If OK then check

the air pressure switch

wiring. If still not working

try another air pressure

switch. If still not working,

change the BMM.

AUTOMATIC/MANUAL

23

The air pressure

switch doesn't

switch off.

Ignition is

inhibited.

Disconnect the air proving

switch. If problem goes

away install a new switch.

If not, check the wiring. If

wiring OK then change

BMM.

AUTOMATIC