4 bms setup as master to c-more boiler controllers, Modbus, Communication – AERCO Modbus Communications Manual User Manual

Page 78: Gf-114

background image

GF-114

MODBUS

Communication

Chapter 5

OMM-0035_0C

USER MANUAL

C-More/BMS Software Setup

Page

78 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

display. Press the ▲ and ▼ arrow keys to set the required address for the BMS on the

Modbus Network.

5. Press the

AIR TEMP key again until NETWORK TIMEOUT is shown in the top line of the

display. Press the ▲ and ▼ arrow keys to select the maximum allowable time (in

seconds) for the EMS (or BAS) to refresh the Remote Setpoint information being sent to

the BMS. AERCO recommends that a time be selected that is at least 3 times the normal

refresh rate. This will allow for the loss of 1 or 2 transmissions without timing out.

6. Press the

AIR TEMP key again until REMOTE SIGNAL is shown in the top line of the

display. Press the ▲ or ▼ arrow key to select MODBUS.

7. Press the

FIELD ADJ key to exit the Field Adjust Mode. The yellow LED on the key

should go off.

8. To set the BMS for Remote Operation, press the

CONFIG SYS key to enter the System

Configuration Mode. The red LED on the key will light.

9. Press the

FIELD ADJ key until HDR SET MODE is shown in the top line of the display.

Press the ▲ and ▼ arrow keys to select REMOTE SET TEMP.

10. Press the

CONFIG SYS key to exit the System Configuration Mode. The red LED on the

key will go off.

The BMS is now programmed for Remote Setpoint Operation from an EMS Master. In the event

of a Modbus signal interruption, AERCO recommends that the TEMP FAIL MODE setting be set

to Switch Inputs if you want the BMS to continue running the Boilers in the CONSTANT SET

TEMP Mode. In this case, ensure that the REF TEMP is set to the desired setpoint temperature.

5.4 BMS SETUP AS MASTER TO C-MORE BOILER CONTROLLERS

To set up the BMS as a Master to Control C-More Boiler Slaves, proceed as follows:

1. Press the

FIELD ADJ key on the BMS front panel to enter the Field Adjust Mode. The

yellow LED on the key should be lit.

2. Press the

HDR TEMP key until RS485 BAUDRATE is shown on the top line of the

display. Press the ▲ and ▼ arrow keys if necessary to set the baud rate to 9600.

3. Press the

HDR TEMP key again until MIN SLAVE ADDR is shown in the display. Use

the ▲ and ▼ arrow keys to set the address to zero.

4. Press the

HDR TEMP key again until MAX SLAVE ADDR is shown in the display. Use

the ▲ and ▼ arrow keys to set the address to zero.

5. Press the

HDR TEMP key until NUMBER NETW BLRS is shown on the top line of the

display. Using the ▲ and ▼ arrow keys, set the number to the maximum number of C-

More Boilers that will be controlled on this Modbus Network.

NOTE

DO NOT count the C-More Boilers or Water Heaters that will only

be monitored on the Modbus Network. Only count the Boilers that

will be controlled by the BMS using the Modbus connection.

6. Press the

HDR TEMP key until MODBUS CNTL TYPE is shown on the top line of the

display. Using the ▲ or ▼ arrow key, if necessary, set it to ROUND ROBIN.

7. Press the

HDR TEMP key until NETW BOILER 1 is shown on the top line of the display.

Use the ▲ and ▼ arrow keys to set the address of the first Boiler being controlled on the