Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual
Page 91

Appendix A
MODBUS
Communication
GF-114
Status Messages & Equations
USER MANUAL
OMM-0035_0C
05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Page
91 of 200
Table A-2: C-More Status And Fault Messages - (Continued)
CODE
MESSAGE
DESCRIPTION
49
WAIT IGNITION RETRY
Second ignition trial after fault.
50
WAIT FAULT PURGE
Post purge after fault.
51
WAIT RETRY PAUSE
30 sec. pause before ignition retry.
52
EXHAUST TEMP SENSOR SHORT
Exhaust temperature sensor is shorted.
53
EXHAUST TEMP SENSOR OPEN
Exhaust temperature sensor is open.
54
WARNING EXHAUST TEMP HIGH
Exhaust temperature is close to alarm limit.
55
EXHAUST_TEMP_HIGH
Exhaust temperature has exceeded the alarm limit.
56
INLET WATER TEMP SENSOR SHORT
Inlet water temperature sensor is shorted.
57
INLET_WATER TEMP SENSOR OPEN
Inlet water temperature sensor is open.
58
WARNING IN WATER TEMP HIGH
Inlet water temperature is nearing the alarm limit.
59
WARNING IN WATER TEMP LOW
Inlet water nearing freezing temperature.
60
IINLET GAS PRESS SENSOR OPEN
Inlet gas pressure sensor connection input is open.
61
GAS PLATE DP SENSOR OPEN
Gas plate differential pressure sensor input is open.
62
INLET_WATER_FLOW_SENSOR_OPEN Inlet water flow sensor input is open.
63
WARNING IN WTR FLOW LOW
Inlet water flow is too low.
64
INLET_WATER HIGH_FLOW
Inlet water flow is too high.