beautypg.com

Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 21

background image

Chapter 2

MODBUS

Communication

GF-114

Standard Register Assignments

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

21 of 200

2.3 BMS/BMS II CONTROLLER STANDARD REGISTER

ASSIGNMENTS

2.3.1 BMS/BMS II Controller Standard Input Register Assignments

The Read Only Input Register address assignments for the BMS/BMS II are listed in Table 2-3

which follows:

Table 2-3: BMS/BMS II Standard Input Register Address Mapping

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

0 (0x0000)

(Reserved)

1 (0x0001)

Header Temperature

40 to 220°F

2 0x0002)

Outside Air

Temperature

-60 to 120°F

3 (0x0003)

Indoor Air/Return

Temperature

40 to 220°F

Indoor Air Temp = BMS

Return Temp = BMS II

4 (0x0004)

Fire Rate Out

0 to 100%

(out to boilers)

5 (0x0005)

Header Set

Temperature

40 to 220°F

6 (0x0006)

Network Address

128 to 247

Default = 128

(If Address = 0, BMS/ BMS II

is Off-Line as a Slave)

7 (0x0007)

Total Boilers Fired

0 to 40 (for BMS)

0 to 32 (for BMS II)

8 (0x0008)

Total Boilers On Line

0 to 40 (for BMS)

0 to 32 (for BMS II)

9 (0x0009)

(Reserved)

10 (0x000A)

Fault/Message Code

0 to 65535

Bit:

0 = Outside Air Sensor

1 = Header Sensor Error

2 = Interlock 1 Error

3 = Interlock 2 Error

4 = Indoor Air Sensor Error/

Return Sensor Error

5 = 4-20mA Input Error

Interpret Bit 4 as follows:

Indoor Air Sensor Error

applies to BMS.

Return Sensor Error applies

to BMS II.

11 (0x000B)

thru

15 (0x000F)

(Reserved)

16 (0x0010)

Lead Boiler Number

1 to 40 (for BMS)

1 to 32 (for BMS II)